34
Application guidelines
CG Drives & Automation 01-5980-01r2
.
Table 15
Application Functions List
Application
Challenge
Emotron TSA Solution
Menu/Chapter
PUMP
Non-linear ramps
Square torque control for square loads
331=Sqr Torq Ctr
341=Sqr Torq Ctr
Water hammer
Square torque control
340
High current and peaks during starts
Square torque control
330
Pump is going in wrong direction
Phase reversal alarm
444
Dry running
Use load monitor minimum alarm
410
High load due to dirt in pump
Use load monitor maximum alarm
410
COMPRESSOR
Mechanical shock for compressor, motor and
transmissions
Linear torque control
330
Small fuses and low current available.
Linear torque control and current limit
at start.
331=Lin Torq Ctr
335
Screw compressor going in wrong direction
Phase reversal alarm
444
Damaged compressor if liquid ammonia
enters the compressor screw.
Use load monitor maximum alarm
410
Energy consumption due to compressor
running unloaded
Use load monitor minimum alarm
410
BLOWER
Mechanical shock for blower, motor and
transmissions. High start current requires
large cables and fuses.
Torque control ensures smooth starts
that minimise mechanical stress.
Start current is minimised by torque-
controlled start.
331=Lin Torq Ctr
CONVEYOR
Mechanical shocks for transmissions and
transported goods.
Linear torque control
330
Loading or unloading conveyors
Slow speed and accurate position
control.
350
600
Conveyor jammed
Use load monitor maximum alarm
410
Conveyor belt or chain is off but the motor is
still running
Use load monitor minimum alarm
410
Starting after screw conveyor has stopped
due to overload.
JOG in reverse direction and then
starting in forward.
Conveyor blocked when starting
Locked rotor function
422
FAN
High starting current in end of ramps
Square torque control for square load
characteristics
330
Slivering belts.
Fan is going in wrong direction when starting.
Catching the motor and stopping
smoothly to zero speed and then
starting in right direction.
331=Sqr Torq Ctr
Belt or coupling broken
Use load monitor minimum alarm
410
Blocked filter or closed damper.
PLANER
High inertia load with high demands on
torque and current control.
Linear torque control gives linear
acceleration and low starting current.
330
Need to stop quickly both for emergency and
production efficiency reasons.
Dynamic vector brake without contactor
for medium loads.
341=Brake
344=Dyn Vect Brk
347
Reverse current brake with external
contactor for heavy loads.
341=Brake
344=Rev Curr Brk
High speed lines
Conveyor speed set from planer shaft
power analogue output.
530
Worn out tool
Use load monitor maximum alarm
410
Broken coupling
Use load monitor minimum alarm
410
Summary of Contents for emotron TSA Series
Page 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Page 2: ......
Page 4: ......
Page 6: ...2 CG Drives Automation 01 5980 01r2...
Page 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Page 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Page 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Page 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Page 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Page 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Page 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Page 160: ...156 Options CG Drives Automation 01 5980 01r2...
Page 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Page 202: ...CG Drives Automation 01 5980 01r2 198...
Page 203: ......