CG Drives & Automation 01-5980-01r2
Connections
17
Emotron TSA frame size 3
Fig. 13 Mains and motor connections for Emotron TSA Size 3.
1. 3-phase mains supply connection,
L1, L2, L3
2. Protective earth (PE) connection for mains supply
3. Motor power supply connection
T1, T2, T3
4. Motor earth,
connection
PE
T1
T2
T3
L1
L2
L3
3
4
2
1
WARNING!
Leakage current may occur from the
thyristors when a 3-phase mains supply is
connected. Full voltage can be detected if no
motor is connected.
Table 8
Tightening torque for bolts [Nm (Lb-in)].
TSA
Frame size
Tightening torque for bolts
[Nm (Lb-in)]
Motor or mains
cables
PE cable
3
20 (177)
12 (106)