Energy Pulse
supports the configuration of the
LED EN Pulse
and
Pulse Constant
setup parameters.
Figure 3-73 Energy Pulse Setup Interface
The following table illustrates the range of Energy Pulse setup parameters where * indicates the default value.
Setup Parameter
Definition
Options
LED EN Pulse
Front Panel LED Energy Pulse Enable
Disable*, kWh Imp. / kWh Exp. / kWh Tot.
/kvarh Imp. / kvarh Exp. / kvarh Tot.
Pulse Constant
Specify the Energy Pulse Constant in number of impulses per kxh
1000*/3200/5000/6400/12800
Table 3-12 Energy Pulse Setup Range
•
IER
supports the configuration of the IER (Interval Energy Recorder) Log.
Figure 3-74 IER Log Setup Interface
The following table illustrates the IER setup parameters where * indicates the default value.
Setup Parameter
Description
Options
Record Mode
Recording Mode
Disable/FIFO*/Stop When Full
Record Interval
Recording Interval in minutes
1 to 65535 min, 15 min*
Start Date
Start Date
-
Start Time
Start Time
-
Recording Depth
Recording Depth
1-65535, 5760*
Parameter 1
--
kWh Import*, kWh Export, kvarh Import, kvarh Export, kVAh Total
Parameter 2
--
kWh Export*, kWh Import, kvarh Import, kvarh Export, kVAh Total
Parameter 3
--
kvarh Import*, kWh Import, kWh Export, kvarh Export, kVAh Total
Parameter 4
--
kvarh Export*, kWh Import, kWh Export, kvarh Import, kVAh Total
Parameter 5
--
kVAh Total*, kWh Import, kWh Export, kvarh Import, kvarh Export
Table 3-13 IER Log Setup Parameters