CET Electric Technology
102
Register
Property
Description
Format
17200~17223
RW
Daily Profile #1
See
17224~17247
RW
Daily Profile #2
17248~17271
RW
Daily Profile #3
17272~17295
RW
Daily Profile #4
17296~17319
RW
Daily Profile #5
17320~17343
RW
Daily Profile #6
17344~17367
RW
Daily Profile #7
17368~17391
RW
Daily Profile #8
17392~17415
RW
Daily Profile #9
17416~17439
RW
Daily Profile #10
17440~17463
RW
Daily Profile #11
17464~17487
RW
Daily Profile #12
17488~17511
RW
Daily Profile #13
17512~17535
RW
Daily Profile #14
17536~17559
RW
Daily Profile #15
17560~17583
RW
Daily Profile #16
17584~17607
RW
Daily Profile #17
17608~17631
RW
Daily Profile #18
17632~17655
RW
Daily Profile #19
17656~17679
RW
Daily Profile #20
Table 5-56 TOU #2’s Daily Profile Setup
Offset
Property
Description
Format
Note
+0
RW
Period #1 Start Time
UINT16
0x0000
+1
RW
Period #1 Tariff
UINT16
0=T1, …, 7=T8
+2
RW
Period #2
Start Time
High-order Byte: Hour
UINT16
0 ≤ Hour < 24
Low-order Byte: Min
Min = 0, 15, 30, 45
+3
RW
Period #2 Tariff
UINT16
0=T1, …, 7=T8
+4
RW
Period #3 Start Time
UINT16
See Period #2 Start Time
+5
RW
Period #3 Tariff
UINT16
0=T1, …, 7=T8
+6
RW
Period #4 Start Time
UINT16
See Period #2 Start Time
+7
RW
Period #4 Tariff
UINT16
0=T1, …, 7=T8
+8
RW
Period #5 Start Time
UINT16
See Period #2 Start Time
+9
RW
Period #5 Tariff
UINT16
0=T1, …, 7=T8
+10
RW
Period #6 Start Time
UINT16
See Period #2 Start Time
+11
RW
Period #6 Tariff
UINT16
0=T1, …, 7=T8
+12
RW
Period #7 Start Time
UINT16
See Period #2 Start Time
+13
RW
Period #7 Tariff
UINT16
0=T1, …, 7=T8
+14
RW
Period #8 Start Time
UINT16
See Period #2 Start Time
+15
RW
Period #8 Tariff
UINT16
0=T1, …, 7=T8
+16
RW
Period #9 Start Time
UINT16
See Period #2 Start Time
+17
RW
Period #9 Tariff
UINT16
0=T1, …, 7=T8
+18
RW
Period #10 Start Time
UINT16
See Period #2 Start Time
+19
RW
Period #10 Tariff
UINT16
0=T1, …, 7=T8
+20
RW
Period #11 Start Time
UINT16
See Period #2 Start Time
+21
RW
Period #11 Tariff
UINT16
0=T1, …, 7=T8
+22
RW
Period #12 Start Time
UINT16
See Period #2 Start Time
+23
RW
Period #12 Tariff
UINT16
0=T1, …, 7=T8
Table 5-57 Daily Profile Data Structure
Notes:
1)
Daily Profile #1’s Period #1 Start Time
is always 00:00 and cannot be modified.
2)
Setting a Period’s
Start Time
as 0xFFFF terminates the Daily Profile’s settings. All later Daily Profile’ setup parameters will be ignored
,
and the previous Period’s duration is from its
Start Time
to the end of the day.
3)
The minimum interval of a period is 15 minutes.
4)
The
Start Time
of a particular Period must be later than the previous Period’s.
5.10.7.4
Alternate Days
Each Alternate Day is assigned a Daily Profile and has a higher priority than Season. If a particular date is set as
an Alternate Day, its assigned Daily Profile will override the “normal” Daily Profile for this day according the TOU
settings.
The iMeter 6 has two sets of Alternate
Days setup parameters, one for each TOU. The Base Addresses for the
two sets are 16700 and 17700, respectively, where the Register Address = Base A Offset. For example,
the register address for TOU #2’s Alternative Day #2’s Date is 17700+3 = 17703.