CET Electric Technology
109
Appendix B – Data Recorder Default Settings
Parameter
DR 1 (HS)
DR 2 (HS)
DR 3 (HS)
DR 4 (HS)
Trigger Mode
Disabled
Disabled
Disabled
Disabled
Recording Mode
Stop-When-Full
Stop-When-Full
Stop-When-Full
Stop-When-Full
Recording Depth
0
0
0
0
Recording
Interval
2
2
2
2
Recording Offset
0
0
0
0
Number of
Parameters
0
0
0
0
Parameter 1~16
Null
Null
Null
Null
Parameter
DR 5
DR 6
DR 7
DR 8
Trigger Mode
Triggered by Timer
Triggered by Timer
Triggered by Timer
Triggered by Timer
Recording Mode
First-In-First-Out
First-In-First-Out
First-In-First-Out
First-In-First-Out
Recording Depth
3360
1440
1440
1440
Recording
Interval
900
900
900
900
Recording Offset
0
0
0
0
No. of
Parameters
6
15
16
6
Parameter 1
kWh Import
Uab
Uan
Uan THD
Parameter 2
kWh Export
Ubc
Ubn
Ubn THD
Parameter 3
kWh Total
Uca
Ucn
Ucn THD
Parameter 4
kvarh Import
Ull avg
Uln avg
Ia THD
Parameter 5
kvarh Export
Ia
kWa
Ib THD
Parameter 6
kvarh Total
Ib
kWb
Ic THD
Parameter 7
Null
Ic
kWc
Null
Parameter 8
Null
I avg
kvara
Null
Parameter 9
Null
kW Total
kvarb
Null
Parameter 10
Null
kvar Total
kvarc
Null
Parameter 11
Null
kVA Total
kVAa
Null
Parameter 12
Null
PF Total
kVAb
Null
Parameter 13
Null
Freq
kVAc
Null
Parameter 14
Null
U2 Unbalance
PFa
Null
Parameter 15
Null
I2 Unbalance
PFb
Null
Parameter 16
Null
Null
PFc
Null
Parameter
DR 9
DR 10
DR 11
DR 12
Trigger Mode
Triggered by Timer
Triggered by Timer
Triggered by Timer
Triggered by Timer
Recording Mode
First-In-First-Out
First-In-First-Out
First-In-First-Out
First-In-First-Out
Recording Depth
1440
1440
1440
1440
Recording
Interval
900
900
900
900
Recording Offset
0
0
0
0
No. of
Parameters
15
16
6
15
Parameter 1
Uab Demand
Uan Demand
Uan THD Demand
Uab max per Demand
Period
Parameter 2
Ubc Demand
Ubn Demand
Ubn THD Demand
Ubc max per Demand
Period
Parameter 3
Uca Demand
Ucn Demand
Ucn THD Demand
Uca max per Demand
Period
Parameter 4
Ull avg Demand
Uln avg Demand
Ia THD Demand
Ull avg max per Demand
Period
Parameter 5
Ia Demand
kWa Demand
Ib THD Demand
Ia max per Demand
Period
Parameter 6
Ib Demand
kWb Demand
Ic THD Demand
Ib max per Demand
Period
Parameter 7
Ic Demand
kWc Demand
Null
Ic max per Demand
Period
Parameter 8
I avg Demand
kvara Demand
Null
I avg max per Demand
Period
Parameter 9
kW Total Demand
kvarb Demand
Null
kW Total max per
Demand Period
Parameter 10
kvar Total Demand
kvarc Demand
Null
kvar Total max per
Demand Period
Parameter 11
kVA Total Demand
kVAa Demand
Null
kVA Total max per
Demand Period
Parameter 12
PF Total Demand
kVAb Demand
Null
PF Total max per Demand
Period
Parameter 13
Freq Demand
kVAc Demand
Null
Freq max per Demand
Period
Parameter 14
U2 Unbalance Demand
PFa Demand
Null
U2 Unbalance max per
Demand Period
Parameter 15
I2 Unbalance Demand
PFb Demand
Null
I2 Unbalance max per
Demand Period
Parameter 16
Null
PFc Demand
Null
Null
Parameter
DR 13
DR 14
DR 15
DR 16
Trigger Mode
Triggered by Timer
Triggered by Timer
Triggered by Timer
Triggered by Timer
Recording Mode
First-In-First-Out
First-In-First-Out
First-In-First-Out
First-In-First-Out
Recording Depth
1440
1440
1440
1440
Recording
900
900
900
900