CET Electric Technology
65
The iMeter 6 provides the following Logical Module Triggers:
Key
Action
Key
Action
0
None
8-19
DR1 to DR12
1-3
DO1 to DO3
20, 21
WR1, WR2
4-7
HSDR1 to HSDR4
22
Alarm Email
Table 4-15 Logical Module Triggers
4.6
Logging
4.6.1
Max./Min. Log
The iMeter 6 records the
Max. Log
and
Min. Log
of
This Month
(Since Last Reset)
and
Last Month
(Before Last
Reset)
with timestamp for the parameters in
. Each log includes the relevant parameter value and its timestamp. The recorded data is stored in the device’s
non-volatile memory and will not suffer any loss in the event of power failure. All of the maximum and minimum
data can be accessed via the Front Panel, Web Interface or through communications.
Max./Min. Parameters
Uan
Ubn
Ucn
Uln avg
Uab
Ubc
Uca
Ull avg
Ia
Ib
Ic
I avg.
kW Total
kvar Total
kVA Total
PF Total
Uan/Uab THD
Ubn/Ubc THD
Ucn/Uca THD
I4
Ia THD
Ib THD
Ic THD
Frequency
Ia K-Factor
Ib K-Factor
Ic K-Factor
Ir Calculated
I2 Unbalance
U2 Unbalance
I0 Unbalance
U0 Unbalance
Table 4-16 Max./Min. Log
The same
Self-Read Time
for the
Peak Demand Log
is used to specify the Max./Min. Log self-read operation.
Please refer to
Section 4.2.5
for a complete description of the
Self-Read Time
and its operation. The Max./Min.
Log of This Month (Since Last Reset) can be reset manually via the Front Panel, Web Interface or communications.
4.6.2
Peak Demand Log
The iMeter 6 stores the
Peak Demand
of
This Month
(Since Last Reset)
and
Last Month (Before Last Reset)
with
timestamp for Ia, Ib, Ic, kW Total, kvar Total and kVA Total. All Peak Demand data can be accessed via the Front
Panel, Web Interface or communications. Please refer to
Section 4.2.5
for a complete description of the
Self-
Read Time
and its operation.
The Peak Demand of This Month can be reset manually via the Front Panel, Web Interface or communications.
The iMeter 6 provides the following Peak Demand parameters:
Peak Demand Logs of This Month (Since Last Reset) and Last Month (Before Last Reset)
kW Total
Ia
kVA Total
Ib
kvar Total
Ic
Table 4-17 Peak Demand Measurements
4.6.3
Interval Energy Recorder (IER) Log
The iMeter 6 provides an Interval Energy Recorder capable of recording the interval energy consumption for
kWh/kvarh Import/Export and kVAh. If the users wish to record the accumulative energy values instead of the
interval energy consumption, the Data Recorder should be used instead. The recorded data is stored in the
device’s non-volatile memory and will not suffer any loss in the event of power failure.
The programming of the IER is supported via the Web Interface or communications. The IER provides the
following setup parameters:
Setup Parameter
Value/Option
Default
Recording Mode
0=Disabled, 1=Stop-When-Full, 2=First-In-First-Out
2
Recording Depth
0 to 65535 (entry)
5760
Recording Interval
0 to 65535 (min)
15
Start Time
20YY/MM/DD, HH:MM:SS
--
Number of Parameters
0 to 5
5
Parameter 1 to 5
kWh Import/Export, kvarh Import/Export and kVAh
--
Table 4-18 IER Setup Parameters
The IER is only operational when the values of
Recording Mode
,
Recording Depth
,
Start Time
and
Number of
Parameters
are all non-zero. When the present time meets or exceeds the
Start Time
, the IER will start to record.