CET Electric Technology
97
5.10.3.2
Logical Module Setup Data Structure
Register
Property
Description
Format
Range
Default
+0
RW
Enable Logical Module
UINT16
0=Disabled, 1=Enabled
0
+1
RW
Mode 1
UINT16
0=AND, 1=OR
2=NAND, 3=NOR
0
+2
RW
Mode 2
UINT16
0
+3
RW
Mode 3
UINT16
0
+4
RW
Source 1
1
UINT16
0 to 24
1
+5
RW
Source 2
1
UINT16
0 to 24
2
+6
RW
Source 3
1
UINT16
0 to 24
3
+7
RW
Source 4
1
UINT16
0 to 24
4
+8
RW
Trigger 1
2
UINT16
0 to 22
0
+9
RW
Trigger 2
2
UINT16
0 to 22
0
Table 5-44 Logical Module Data Structure
Notes:
1)
The Logical Modules can have up to 4 Source inputs.
Table below provides a list of Logical Module Sources.
Key
Source
Key
Source
0
None
13
Setpoint #13 (Standard)
1
Setpoint #1 (Standard)
14
Setpoint #14 (Standard)
2
Setpoint #2 (Standard)
15
Setpoint #15 (Standard)
3
Setpoint #3 (Standard)
16
Setpoint #16 (Standard)
4
Setpoint #4 (Standard)
17
Setpoint #17 (High-Speed)
5
Setpoint #5 (Standard)
18
Setpoint #18 (High-Speed)
6
Setpoint #6 (Standard)
19
Setpoint #19 (High-Speed)
7
Setpoint #7 (Standard)
20
Setpoint #20 (High-Speed)
8
Setpoint #8 (Standard)
21
Setpoint #21 (High-Speed)
9
Setpoint #9 (Standard)
22
Setpoint #22 (High-Speed)
10
Setpoint #10 (Standard)
23
Setpoint #23 (High-Speed)
11
Setpoint #11 (Standard)
24
Setpoint #24 (High-Speed)
12
Setpoint #12 (Standard)
Table 5-45 Logical Module Sources
2)
Trigger
1/2
specifies what action the Logical Module will take when it becomes active. Table 5-42 below provides a list of Logical
Module Triggers.
Key
Action
Key
Action
0
None
12
HS DR #5
1
DO1
13
HS DR #6
2
DO2
14
HS DR #7
3
DO3
15
HS DR #8
4
DR #1
16
HS DR #9
5
DR #2
17
HS DR #10
6
DR #3
18
HS DR #11
7
DR #4
19
HS DR #12
8
HS DR #1
20
WFR #1
8
HS DR #2
21
WFR #2
10
HS DR #3
22
Alarm Email
11
HS DR #4
Only when
DOx Mode
is set to
Remote Control
would setting
Setpoint Trigger
to
DOx
be valid.
Table 5-46 Logical Module Triggers
5.10.4
Data Recorder Setup
5.10.4.1
Data Recorder Setup Registers
Register
Property
Description
Format
7000~7022
RW
Data Recorder #1 (High-Speed)
See
Section 5.10.4.2
7023~7045
RW
Data Recorder #2 (High-Speed)
7046~7068
RW
Data Recorder #3 (High-Speed)
7069~7091
RW
Data Recorder #4 (High-Speed)
7092~7114
RW
Data Recorder #5 (Standard)
See
Section 5.10.4.3
7115~7137
RW
Data Recorder #6 (Standard)
7138~7160
RW
Data Recorder #7 (Standard)
7161~7183
RW
Data Recorder #8 (Standard)
7184~7206
RW
Data Recorder #9 (Standard)
7207~7229
RW
Data Recorder #10 (Standard)
7230~7252
RW
Data Recorder #11 (Standard)
7253~7275
RW
Data Recorder #12 (Standard)
7276~7298
RW
Data Recorder #13 (Standard)
7299~7321
RW
Data Recorder #14 (Standard)
7322~7344
RW
Data Recorder #15 (Standard)
7345~7367
RW
Data Recorder #16 (Standard)
Table 5-47 Data Recorder Setup Registers