Demands
▪
Demands and Predicted Demands for 3-Phase Voltage, Current, Power, PF, I4, Frequency, U and I Unbalance
and THD
▪
Peak Demands with Timestamp for Current, Power, and PF of This Month and Last Month (or Since Last
Reset and Before Last Reset)
▪
Max/Min values per demand interval
▪
Demand synchronization with DI
Setpoints
▪
16 Standard Setpoints with extensive list of monitoring parameters including Voltage, Current, Power,
Demands and THD, etc.
▪
8 High-Speed Setpoints for Voltage, Current, Power, PF, Frequency, Deviation, and DI.
▪
Configurable thresholds and time delays
▪
6 Logical Modules supporting AND/OR/NAND/NOR operations
▪
SOE, WF Recording, Data Recorder, DO, and Email Alarm trigger
Multi-Tariff TOU Capability
▪
Two independent sets of TOU Schedules
o
Up to 12 Seasons
o
90 Holidays or Alternate Days
o
20 Daily Profiles, each with 12 Periods with minimum 15-minute interval
o
8 Tariffs, each providing kWh/kvarh Import/Export and kVAh
▪
Switching between two TOU schedules according to pre-programmed time and logged as SOE event
▪
Tariff switching based on DI status
Log memory
▪
1GB on-board memory
▪
Data Recorder Logs, Waveform Recorder Logs, Energy Log and Demand Logs
Data Recorder (DR) Log
▪
12 Standard DR Logs and 4 High-Speed DR Logs
▪
Recording interval from 1s to 40 days for standard DR and 1 to 60 cycles for High-Speed DR.
▪
Up to 16 Programmable Parameters for each DR Log with programmable sources which include almost all
Real-Time measurements, Harmonics, Unbalance and Demand measurements
▪
Configurable Depth and Recording Offset
▪
Support FIFO or Stop-When-Full Recording Mode
Waveform Recorder (WFR) Log
▪
2 independent groups of Waveform Recorders with a combined total of 256 entries
▪
Simultaneous capture of 3-Phase Voltage and Current signals
▪
Programmable formats and pre-fault cycles from 256x20 to 16x320
▪
Support FIFO Recording Mode
Interval Energy Recorder (IER) Log
▪
Interval Energy recording of kWh/kvarh Import/Export and kVAh Total
▪
Support FIFO or Stop-When-Full Recording Mode
SOE Log
▪
512 events time-stamped to ±1ms resolution
▪
Setup Changes, Setpoint events and I/O Operations
PQ Log
▪
512 entries time-stamped to ±1ms resolution
▪
Sag/Swell/Interruption and Transient detection
Max/Min Log
▪
Logging of Max./Min. values for measurements such as Voltage, Current, Frequency, kW, kvar, kVA, PF,
Unbalance, K-factor, and THD with Timestamp for This Month and Last Month (or Since Last Reset and Before
Last Reset)