CET Electric Technology
75
5)
The range of the SOE/PQ/WFR/IER/DR Log Pointer is between 0 and 0xFFFFFFFFH. The pointer is incremented for every new log
generated and will roll over to 0 if its current value is 0xFFFFFFFFH. A value of zero indicates that the specific Log does not contain any
record. If a
Clear SOE Log/PQ Log/WFR Log/IER Log/DR Log
is performed from the Front Panel/Web Interface or via communications,
its corresponding
Log Pointer
will be reset to zero. Use the following equation to determine the latest log location:
Latest Log Location = Modulo [
Log Pointer / Log Depth
]
Where
Log Depth
= 512 for
SOE Log
and
PQ Log
, 128 for
WFR Log
,
IER Recording Depth
for
IER
Log
and
DR Recording Depth
for
DR
Log
.
6)
The
Device Operating Time
means the accumulated Operating Time (or Running Hours) whenever any per-phase Current has
exceeded the
Current on Threshold
(Register 6200). The
Device Operating Time
data is stored in non-
volatile
memory and will not
suffer any loss in the event of a power failure.
5.2
Energy Measurements
5.2.1
Total Energy Measurements
The Energy registers have a maximum value of 1,000,000,000 and will roll over to zero automatically when it is
reached. The iMeter 6 also provides energy measurements in fractional values if they are required. Using the
“Fractional” registers, having units such as W
sec, var
sec and VA
sec, the user can obtain decimal resolution for
achieving higher accuracy. For example, if the value of the kWh fractional register is 3200000 W
sec, the decimal
value is 3200000/3600000=0.8889kWh. If the higher resolution is not required, it is not necessary to read the
fractional energy registers.
Register
Property
Description
Format
Scale
Unit
0200
RW
kWh Import
UINT32
x1
kWh
0202
RW
kWh Export
UINT32
0204
RO
kWh Net
INT32
0206
RO
kWh Total
UINT32
0208
RW
kvarh Import
UINT32
x1
kvarh
0210
RW
kvarh Export
UINT32
0212
RO
kvarh Net
INT32
0214
RO
kvarh Total
UINT32
0216
RW
kVAh
UINT32
x1
kVAh
0218
RW
kvarh Q1
UINT32
x1
kvarh
0220
RW
kvarh Q2
UINT32
0222
RW
kvarh Q3
UINT32
0224
RW
kvarh Q4
UINT32
0226
RO
kWh Import Fractional
Float
x1
W
s
0228
RO
kWh Export Fractional
Float
0230
RO
kWh Net Fractional
Float
0232
RO
kWh Total Fractional
Float
0234
RO
kvarh Import Fractional
Float
x1
var
s
0236
RO
kvarh Export Fractional
Float
0238
RO
kvarh Net Fractional
Float
0240
RO
kvarh Total Fractional
Float
0242
RO
kVAh Fractional
Float
x1
VA
s
0244
RO
kvarh Q1 Fractional
Float
x1
var
s
0246
RO
kvarh Q2 Fractional
Float
0248
RO
kvarh Q3 Fractional
Float
0250
RO
kvarh Q4 Fractional
Float
Table 5-3 Energy Measurements
5.2.2
Phase A Energy Measurements
Register
Property
Description
Format
Scale
Unit
4600
RW
kWh Import
UINT32
x1
kWh
4602
RW
kWh Export
UINT32
4604
RW
kWh Net
INT32
4606
RW
kWh Total
UINT32
4608
RW
kvarh Import
UINT32
x1
kvarh
4610
RW
kvarh Export
UINT32
4612
RW
kvarh Net
INT32
4614
RW
kvarh Total
UINT32
4616
RW
kVAh
UINT32
x1
kVAh
4618
RW
kvarh Q1
UINT32
x1
kvarh
4620
RW
kvarh Q2
UINT32
4622
RW
kvarh Q3
UINT32
4624
RW
kvarh Q4
UINT32
4626
RW
kWh Import Fractional
Float
x1
W
s
4628
RW
kWh Export Fractional
Float
4630
RW
kWh Net Fractional
Float