Figure 3-79 TOU – Alternate Days Setup Interface
Click to add a new Alternate Day or to clear the setting for the current Alternate Day.
Figure 3-80 TOU – Alternate Days Setup Interface
3.2.3.5.4
Record
Click
Record
on the left-hand pane to expand its sub-menu which includes
Waveform and DR
(Data Recorder).
3.2.3.5.4.1
Waveform
The iMeter 6 provides 2 independent groups of Waveform Recorders (
WFR
) with 128 entries each. Click on
WFR1
or
WFR2
to access their configurations. Please refer to
Section 4.6.4
for more details.
The following table illustrates the setup range for WFR 1/ 2 parameters, where * indicates the default value.
Setup Parameters
Value/Option
Default
WFR 1
WFR 2
Format
256x20, 128x40, 64x80, 32x160, 16x320
256x20
256x20
Pre-fault Cycles
0 to 20 Cycles
4
6