Overview of wireless sensors
Wireless Sensors
CARRIER CORPORATION ©2018
Installation Guide
All rights reserved
15
Specifications
Power requirements
24 Vac or 24 Vdc ±10% @ 125 mA
Power supply
24 Vac or 24 Vdc external power supply, Class 2
Protocol
Customized version of EnOcean
Radio frequency
902 MHz (North America) or
868 MHz (Europe and China)
Transmission range
Typically, 60 ft. (18.29 m) maximum from Wireless Adapter, assuming sensor
and Wireless Adapter are separated by no more than 1 drop ceiling or 2 walls
(drywall with metal studs).
Protection
Communication Port is optically isolated.
Operating environment
Indoor rated only
0° to 130°F (-17.8° to 54.4°C)
10% to 90% relative humidity (non-condensing)
Housing
UL94-5VA plenum rated enclosure, rugged GE C2950 Cycoloy plastic,
black color
Weight
4.3 oz. (121.9 g)
Dimensions
4.66 in. x 3.36 in. 1.39 in.
(11.84 cm x 8.53 cm x 3.53 cm)
Compliance
United States of America:
FCC CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class B
Contains FCC ID: SZV-STM300U
Canada:
Industry Canada Compliant, ICES-003, Class B
cUL Listed UL 916,PAZX&, Energy Management Equipment
Europe:
Mark
EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in
residential, commercial and light industry environment
EN50491-3:2009, Part 3: Electrical safety requirements for Home and
Building Electronic Systems (HBES) and Building Automation and Control
Systems (BACS)
Low Voltage Directive: 2014/35/EU
RoHS Compliant: 2011/65/EU
Australia and New Zealand:
C-Tick Mark, AS/NZS 61000-6-3
Summary of Contents for WIRELESS ADAPTER