Installing the Wireless Adapter and sensors
Wireless Sensors
CARRIER CORPORATION ©2018
Installation Guide
All rights reserved
30
CAUTION
To provide accurate values, a wireless sensor should be in its permanent location for at least 15
minutes before you calibrate it.
To install the Wireless Adapter
(page 30)
To install a Standard or Plus sensor
(page 32)
To install a Pro-F sensor
(page 34)
To install a Motion/Lux sensor
(page 35)
To install a Window/Door sensor
(page 36)
Troubleshooting the wireless sensor installation
(page 39)
To install the Wireless Adapter
Rnet wiring specifications
NOTE
Use the specified type of wire and cable for maximum signal integrity.
Description
4 conductor, shielded or unshielded, CMP, plenum rated cable
Conductor
22 AWG (7x0096) bare copper
Maximum length
500 feet (152 meters)
Insulation
Low-smoke PVC (or equivalent)
Color Code
Black, white, green, red
Shielding
If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire
UL temperature rating
32–167°F (0–75°C)
Voltage
300 Vac, power limited
Listing
UL: NEC CL2P, or better
WARNING
Do not apply line voltage (mains voltage) to the Wireless Adapter.
Installing the Wireless Adapter and sensors