Table 3-1. Unit Data - Continued
* Displays information or setting entered in the microprocessor Configurations
+ May or may not be displayed depending on Parameter/Configuration settings
*
+
PRODUCTSHIELD SETUP: Press “=” to access the list.
PRODUCTSHIELD
ECONO:
Indicates if ProductShield Econo is
OFF
OR
Go To Start-Stop
OR
Go
To Continuous Run
ECONO MIN
TEMP - XX
°
Displays minimum temperature setting for activation of ProductShield
Econo. (Will only be displayed if Econo is
NOT
OFF
)
ECONO MAX
TEMP - XX
°
Displays maximum temperature setting for activation of ProductShield
Econo. (Will only be displayed if Econo is
NOT OFF
)
ECONO
DELTA-T - XX
°
Displays Delta-T setting for activation of ProductShield Econo. (Will only
be displayed if Econo is
NOT OFF
)
PRODUCTSHIELD
HIGH AIR:
Indicates if ProductShield High Air is
OFF
OR
ON
HIGH AIR MIN
TEMP - XX
°
Displays minimum temperature setting for activation of ProductShield
High Air. (Will only be displayed if Econo is
NOT
OFF
)
HIGH AIR MAX
TEMP - XX
°
Displays maximum temperature setting for activation of ProductShield
High Air. (Will only be displayed if Econo is
NOT OFF
)
HIGH AIR
DELTA-T - XX
°
Displays Delta-T setting for activation of ProductShield High Air. (Will
only be displayed if Econo is
NOT OFF
)
PRODUCTSHIELD:
WINTER - XX
°
Indicates ProductShield Winter is OFF or the ambient temperature below
which ProductShield Winter will be active.
*
+
RANGE 1 LOCK
This is only displayed when Range Lock 1 is configured ON.
Displays Range Lock 1 setting:
OFF = Temperature Range 1 Lock is turned off.
CONTINUOUS = When the set point is set between Range 1 Minimum
& Maximum Temperatures, the unit is set to operate only in Continuous.
START-STOP - When the set point is set between Range 1 Minimum &
Maximum Temperatures, the unit is set to operate only in Start-Stop.
*
+
RANGE 1 MINIMUM TEMP
Displays minimum temperature setting for Range 1. (Will only be dis-
played if Range Lock 1 is
ON
)
*
+
RANGE 1 MAXIMUM TEMP Displays maximum temperature setting for Range 1. (Will only be dis-
played if Range Lock 1 is
ON
)
*
+
RANGE 2 LOCK
This is only displayed when Range Lock 1 is configured ON.
Displays Range Lock 1 setting:
OFF = Temperature Range 2 Lock is turned off.
CONTINUOUS = When the set point is set between Range 2 Minimum
& Maximum Temperatures, the unit is set to operate only in Continuous
Run.
START-STOP = When the set point is set between Range 2 Minimum &
Maximum Temperatures, the unit is set to operate only in Start-Stop.
*
+
RANGE 2 MIN. TEMP
Displays minimum temperature setting for Range 2. (Will only be dis-
played if Range Lock 2 is
ON
)
*
+
RANGE 2 MAX. TEMP
Displays maximum temperature setting for Range 2. (Will only be dis-
played if Range Lock 2 is
ON
)
*
+
TEMPERATURE (REMOTE)
SENSOR (1, 2 or 3)
Will only display when one or more of the optional sensors are con-
figured ON. Displays temperate reading of remote Temperature Sensor 1
(2, or 3).
*
DATALOGGER (DataLink
data recorder)
Displays the current Date and Time that the DataLink data recorder is
using. This may be different than local time, depending on the Time
Zone and Daylight Savings.