The TV-UC561 also has the following ports:
•
Rnet port for connecting ZS sensors, an Equipment Touch, an TruVu™ ET Display, and Wireless Adapter for
wireless sensors
•
Service USB port for connecting locally to controller setup pages, the TruVu™ ET Display, or the Carrier
wireless service adapter
•
Comm USB port for other communication options in the future
•
Act Net port supports a combination of up to 5 Act Net addresses, as follows:
○
Address
1
is reserved for the Carrier actuator
○
Address
2
and
3
are reserved for the VAV Zone II Secondary Duct
○
Address
4
and
5
for i-Vu® Smart Valves
Specifications
Driver
drv_fwex_< version >.driverx
Maximum number of control programs*
1
Maximum number of BACnet objects*
12000
Third-party BACnet integration points
NOTE
Must be on the BACnet/IP network
100
* Depends on available memory.
Power
24 Vac ±15%, 50
–
60 Hz, 55 VA
24 Vdc ±10%, 20 W
NOTE
The above power consumption is for the controller only. Adding devices to
the Act Net bus increases total power consumed.
Eth0, Eth1
10/100 BaseT, full duplex, Ethernet ports for BACnet/IP and/or BACnet/Ethernet,
or Modbus TCP/IP communication.
Under normal operation, network traffic not destined for this controller is repeated
to the other Ethernet port. When the controller is powered off, all traffic received on
one port is mirrored to the other port.
Rnet port
•
Supports up to 5 wireless and/or ZS sensors, and one Equipment Touch or
TruVu™ ET Display
•
Supplies 12 Vdc/260 mA power to the Rnet across its rated temperature
range.
NOTE Ambient temperature and power source fluctuations exceeding the
listed operating ranges may reduce the power supplied by the Rnet port.
NOTE
If the total power required by the sensors on the Rnet exceeds the
power supplied by the Rnet port, use an external power source. The Wireless
Adapter, Equipment Touch, or TruVu™ ET Display must be powered by an
external power source. See the specifications in each device's Installation and
Start-up Guide to determine the power required.