Wiring for communications
TruVu™ UC561
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
14
The TV-UC561 communicates on the following ports.
Port
Protocol
Port type(s)
Speed(s)
Eth0
Eth1
BACnet/IP
BACnet/Ethernet
Ethernet
10 or 100 Mbps
Service port
*
USB 2.0
USB
Comm Port
(future use)
USB 2.0
USB
Rnet Port
See
Wiring devices to the TV-UC561's Rnet port
(page 16).
Act Net Port
See
Wiring devices to the TV-UC561's Act Net port
(page 17).
*
See
To set up the controller through the Service port
(page 43).
Wiring specifications
For...
Use...
Maximum Length
Ethernet - not
daisy chained
Cat5e or higher Ethernet cable
328 feet (100 meters)
Ethernet - a
daisy chain
configuration
Cat5e or higher Ethernet cable
164 feet (50 meters)
WARNINGS
•
Do not apply line voltage (mains voltage) to the controller's ports and terminals.
•
Do not exceed the minimum bend radius of the Cat5e or Cat6e Ethernet cable. Refer to Ethernet cable
manufacturer specifications for minimum bend radius.