Adjusting the TV-UC561 driver properties
TruVu™ UC561
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
34
Common Alarms
On these pages, you can enable/disable, change BACnet alarm properties, or set delays for the following BACnet
alarms:
Common alarms:
•
Duplicate Address
•
Control Program
•
Controller Halted
•
Locked I/O
•
Program Stopped
•
Excessive COV
•
All Programs Stopped
Controller Generated Alarm
Description
Short message shown on the i-Vu®
Alarms
page or in an alarm action when this
type of alarm is generated.
Events
Alarm Category and Alarm
Template
See
Setting up an alarm source in the i-Vu® interface
in i-Vu® Help.
Enable
Clear these checkboxes to disable Alarm or Return to normal messages of this
type from the TV-UC561.
Notification Class
In a typical i-Vu® system, the Notification Class is 1; however, if needed, you can
associate a different notification class with the alarm. See
Notification Classes
(page 32) to set up alarm delivery options for a specific Notification Class.