Wiring for communications
TruVu™ UC561
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
15
To connect the TV-UC561 to the Ethernet
Connect an Ethernet cable from the building BAS system or another TV-UC561 controller to the Eth0 Ethernet port.
If necessary, connect another Ethernet cable from the Eth1 port to the next TV-UC561 controller in a daisy chain.
The TV-UC561 has a fail-safe Ethernet relay that bypasses a daisy chained controller in the event of an internal
disruption, such as a power loss. When a failure occurs and the switch is bypassing a controller, the network
connection on both sides of the controller are electrically connected, which continues the signal and passes it to
the next controller.
NOTE
If your system has controllers on different IP subnets separated by an IP router, you must configure one
controller on each subnet as a BACnet Broadcast Management Device (BBMD). Do not configure more than one
BBMD per subnet as this may cause circular routes. See "Setting up BACnet Broadcast Management Devices
(BBMDs)" in SiteBuilder or i-Vu® Help.