USER'S GUIDE

TITLE: PRO-DIALOG CONTROL 4 FOR AIR & WATER COOLED

CHILLERS SERIES 30 GX & HXC VERSION 2

REV: original

Property of CARRIER S.A. Montluel.
Not to be disclosed to persons outside the organization without Written authorization

SYNOPTIQUE CARRIER - AIR-COOLED BI CIRCUIT - ABC PARTNERS 08/06/98

DA

TE

S

P

E

CIFICA

TIO

N

COP

Y

 N°

ECG CARRIER S.A.

 E

C

G-UG-00-001

06/

12/

00

Downloaded from 

www.Manualslib.com

 

manuals search engine

 

Summary of Contents for Pro-Dialog CONTROL 4

Page 1: ...l Property of CARRIER S A Montluel Not to be disclosed to persons outside the organization without Written authorization SYNOPTIQUE CARRIER AIR COOLED BI CIRCUIT ABC PARTNERS 08 06 98 DATE SPECIFICATI...

Page 2: ...Service 1 COMPANY NAME COPY Ba Tung PHAM ORIGINATOR CARRIER SA USER S GUIDE FOR 30GX HX PRO_DIALOG 4 V 2 ECG UG 02 002 Rev original Page 98 CARRIER S A NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER...

Page 3: ...runtime sub menu 31 4 2 5 User Configuration 32 4 2 6 Network Configuration 32 4 2 6 1 General 32 4 2 6 2 Configuring a Control as a Broadcast Acknowledger 32 4 2 6 3 Setting Time and Date 32 4 2 6 4...

Page 4: ...18 5 Reclaim Operation Using Air Cooled Exchanger 52 4 18 6 Reclaim Condenser Water Valve Control 52 4 18 7 Reclaim Condenser Heater Control 52 4 19 Two Units Master Slave Control 53 4 19 1 General 53...

Page 5: ...ting cases For more complete information use the remaining sections and also IOM Second subsection describes all the unit configuration and the methods to modify it The last subsections describe the u...

Page 6: ...temperature control w Motor temperature control w Safety lock control w Quick test function w Diagnostics function w Local Interface Display with Metric units w Digital pressure gauges through the ma...

Page 7: ...ead pressure control mode x x Unit on off schedule control x Compressor Number 1 to 4 Capacity x Economizer Motor cooling TQ valve feedback signal x x x Cooler Heater Select x x Fans 2 Separate Circui...

Page 8: ...E NUMBER This software is referenced under the 15 digits software reference number CSA SR 208410XX The two last digits XX provides the software version e g 2 0 15 digits reference number can be displa...

Page 9: ...32 GB 500 092 EE Local Interface Device 30HX dual circuits 32 GB 500 112 EE Local Interface Device 30GX single circuit 32 GB 500 082 EE Local Interface Device 30HX single circuit 32 GB 500 102 EE This...

Page 10: ...3 4x DO BOARD 2 2 2 2 2 2 1 PD4 EXV BOARD 4 3 2 1 PD4 SCPM BOARD 1 1 1 1 PD4 BASIC BOARD 4 3 2 1 NUMBER OF COMPRESSORS COMPONENTS UNIT TYPE AIR COOLED MORE THAN 2 FAN STAGES if no AUX board or MORE T...

Page 11: ...J4 All Dual setpoint switch 12 J4 All Remote Control switch status 11 J4 All 0 10 VDC setpoint reset signal or demand limit signal 10 J8 All Circuit B suction pressure 9 J7D All Circuit B discharge pr...

Page 12: ...e 3 Current sensor 3 3 J8 Current Phase 2 Current sensor 2 2 J8 Current Phase 1 Current sensor 1 1 J8 Usual Functions Type Channel CT Connector Oil level Dry contact 6 2 J6 High Pressure Dry contact 5...

Page 13: ...ll support 2 fans if circuit has 6 fans 3 fans if circuit has 7 fans 4 fans if circuit has 8 fans 3 1 4 2 Terminal J4 Description 12 12 12 12 12 12 12 12 11 11 11 11 DO 4 DO 4 DO 4 DO 4 DO 3 DO 3 DO 3...

Page 14: ...8 circuit B 8 8 Fan 7 circuit A 3 or 7 circuit B Reclaim option condenser heater 7 7 Fan 6 circuit A 2 or 6 circuit B 6 6 Fan 5 circuit A 1 or 5 circuit B Reclaim valve B 5 5 J3 Fan 4 circuit A or ci...

Page 15: ...otor Coil 4 Coil 3 Coil 2 Coil 1 5 4 3 2 1 Connector J2A J2B Pins description 3 1 7 4xAI 2xAO BOARD This board provides 4 analog inputs labeled AI 1 AI 2 AI 3 and AI 4 on the terminal J2 and 2 analog...

Page 16: ...2 Each output can be independently configured with a bridge allowing to close 2 pair of pins named C or V 6 R 6 R 4 20 mA Varifan circuit B C 6 R 6 R 0 10 Vdc Varifan circuit B V AO 2 5 R 5 R 4 20 mA...

Page 17: ...ption condenser heater Triac DO 4 19 unused Triac DO 3 18 reclaim option or cooler heater option circuit B refrigerant condenser entering solenoid Triac DO_24 17 reclaim option or cooler heater option...

Page 18: ...transducer curve 3 2 2 Large band pressure sensors They are used to measure oil pressures for unit operating with low ambient when large band oil pressure transducer is selected Carrier part OP12DA05...

Page 19: ...see next page They have Carrier Part No HH 79 NZ 047 3 3 1 Discharge gas temperature This is installed on the discharge pipe of each compressor It is used to control the discharge superheat The disch...

Page 20: ...4 18 5 427 4 93 0 1 050 0 65 0 2 990 1 37 0 10 472 3 9 0 45 798 6 19 0 431 8 92 5 1 069 9 64 5 3 051 0 36 5 10 728 8 8 5 47 147 7 19 5 436 3 92 0 1 090 2 64 0 3 113 4 36 0 10 992 1 8 0 48 541 1 20 0 4...

Page 21: ...the Network Service Tool 4 2 2 Main interface configuration sub menu tree structure broAdCASt 7 S HoLidAY 6 M SCHEduLE 2 5 E MAStEr SLAvE SCHEduLE 1 4 T SErViCE 3 dAtE 3 I FACtorY 2 MEnu SErViCE 2 US...

Page 22: ...ux Boards Select Yes No14 No pd4_aux Parameters from 1 to 16 in version 1 x are the same than those in the new version 2 X For Retrofit from verson 1 x to the new 2 x it is better to write down in a p...

Page 23: ...an 4xAI 2xAO board is required and reclaim temperature sensor are used for information only 7 Reclaim option requires an Aquasnap Basic board for reclaim entering and leaving temperatures solenoids an...

Page 24: ...mps amps 0 to 560 cpa2 mta 8 1 Compressor A1 Must Trip Amps amps 0 to 560 cpa1 mta 7 Large Band Oil transducer select yes no oil sel 6 Economizer select yes no econ_sel 5 Varifan or Water valve select...

Page 25: ...O PERSONS OUTSIDE CARRIER ORGANIZATION CARRIER SA USER S GUIDE FOR 30GX HX PRO_DIALOG 4 V 2 ECG UG 02 02 Rev Original Page 24 98 TQ output done TQ output done SCPM A1 SCPM B1 THA THB EXV BOARD Connexi...

Page 26: ...4 to 610 6 zm_spt 17 Maximum Z Multiplier 1 0 to 6 011 6 0 hc_zm 18 Entering Fluid Control Yes No12 No ewt_opt Note this table canl be downloadable at any time However modified value shall not be used...

Page 27: ...ng temperature override threshold then one stage capacity of the corresponding circuit shall be removed doesn t apply to the last stage 8 This decision allows to set the high current override threshol...

Page 28: ...pacity control select cls ctrl 15 Maximum Current differential in percent of MTA curr dif 14 Maximum Current setpoint in percent of MTA curr max 13 Maximum Condensing Temperature differential mct diff...

Page 29: ...s based on the unit on off status w 2 condenser pump is ON when unit is ON compressors are ON 2 This decision is only used for the water cooled chillers w 1 water 2 medium brine 3 low brine w If conde...

Page 30: ...SERVICE2 Unit shall be stopped and service password or factory password are required reclaim SCT control point determination offset B circuit B C rsp b b 16 2 reclaim SCT control point determination...

Page 31: ...table MAINCFG Unit should be stopped and service password or factory password are required Oil filer b2 next service in days displayed only cap b2 0 ofilb2 m 12 1 Oil filer b1 next service in days di...

Page 32: ...llows to view and modify the service configuration table UPDTHOUR Unit shalld be stopped and service password or factory password are required Condenser Pump operating hours Not displayed if cond_ctr...

Page 33: ...date of a Pro dialog controller can be done through the network Setting the correct date and time is necessary for units connected on a network which collects alarms Two methods are available w Throug...

Page 34: ...which can be set to either 0 or 1 Setting a digit to 1 specifies that alarm will be sent to the system element that correspond to that digit Setting all digits to 0 disables alarm processing Digits i...

Page 35: ...e alarms A re alarm occurs when the condition that caused the initial alarm continues to persist for the number of minutes specified in this decision Re alarming will continue to occur at the specifie...

Page 36: ...HIL_S_S CTRL_PNT or DEM_LIM HC_SEL variables has a force priority higher than a control force 2 This timer is started when all conditions to start the lag chiller are satisfied Lag chiller shall not b...

Page 37: ...heck freezing conditions and additional heat to the cooler cooler fluid temp 3 SSTa SSTb 2 Pump shall be turned of if cooler fluid temp 8 C SSTa SSTb 2 w If both saturated suction temperatures of circ...

Page 38: ...essure located at plate exchanger in our application quite the same than economiser pressure With the same economiser pressure the higher heating signal is commanded CPA1_PUL or CPB1_PUL the lower is...

Page 39: ...ply to loaders 4 8 1 2 Z Multiplier calculation The z_multiplier factor allows to indirectly increase the compressor on off time delay In consequence it can be adjusted increased to avoid compressors...

Page 40: ...3 5 6 16 17 18 19 20 21 are active the variable close control cls_ctrl shall be enabled whatever the configuration to allow unloading the last loader in the circuit Chiller Current Override override...

Page 41: ...apply when the reason for a shutdown is due to an alarm condition 7 For any shutdown all compressors and loaders will be shut down at the same time For more than 2 compressors two types of sequencing...

Page 42: ...ing Capacity Logic with close_control NO ON ON 2 ON ON 2 OFF ON 2 ON ON 2 ON ON 1 ON ON 2 ON ON 1 OFF ON 2 ON ON 1 ON ON 1 OFF ON 1 ON ON 1 OFF ON 1 OFF ON 1 OFF OFF 0 ON ON 1 OFF OFF 0 OFF ON 1 OFF O...

Page 43: ...Loading Decreasing Capacity Logic with close_control YES OFF OFF 0 OFF OFF 1 OFF OFF 0 OFF ON 1 OFF OFF 0 ON ON 1 OFF OFF 1 OFF ON 1 OFF ON 1 OFF ON 1 OFF ON 1 ON ON 1 OFF OFF 1 OFF ON 2 OFF ON 1 OFF...

Page 44: ...8 Staged Loading Decreasing Capacity Logic with close_control NO OFF OFF 0 OFF OFF 0 OFF OFF 0 OFF OFF 1 OFF OFF 0 OFF ON 1 OFF OFF 0 ON ON 1 OFF OFF 0 OFF ON 2 OFF OFF 0 ON ON 2 OFF ON 1 ON ON 2 ON...

Page 45: ...ON 2 OFF ON 1 ON ON 2 ON ON 1 ON ON 2 OFF ON 2 ON ON 2 ON ON 2 ON ON 2 LOADER 2 LOADER 1 NUMBER OF COMPRESSORS LOADER 2 LOADER 1 NUMBER OF COMPRESSORS LAG CIRCUIT LEAD CIRCUIT CARRIER SA USER S GUIDE...

Page 46: ...a low condensing temperature the discharge superheat protection can switch from enable to disable in few scans and so on This control uses a kind of auto adaptive method whose goal is to find out the...

Page 47: ...or SCT differential as 55 C 13 F1 OAT 20 c 0 c 68 F 32 F 1 fan 1 fan SCT control point 35 C 95 F 40 C 104 F 35 C 95 F SCT Diff 4 12 1 Air Cooled Condensing Pressure Control Fan staging with Aux board...

Page 48: ...0 total fans fans controlled DO_4 DO_3 DO_2 DO_1 stage 8 fan_1 fan_2 fan_3 fan_4 fan_5 fan_6 fan_7 fan_8 on on on on 8 7 fan_1 fan_3 fan_4 fan_5 fan_6 fan_7 fan_8 on on off on 7 6 fan_1 fan_2 fan_5 fa...

Page 49: ...uit capacity has been reduced due to current override then the circuit capacity increase will not be allowed for 5 minutes what ever current measured This shall avoid compressor cycling 4 16 Stopping...

Page 50: ...iteria For Trip Tested only when the compressor is ON DOP Differential Oil Pressure for the appropriate compressor DOP Oil pressure Economizer pressure Economizer pressure is the common econ_sel YES E...

Page 51: ...ntinue to run 4 17 4 Differential Oil Pressure Setpoint 1 alarm condition summary CARRIER SA USER S GUIDE FOR 30GX HX PRO_DIALOG 4 V 2 ECG UG 02 002 Rev Original Page 50 98 CARRIER S A NOT TO BE DISCL...

Page 52: ...a 10 minutes duration or as soon as pumpdown pressure is lower than 300 kpa 44 psi reclaim injection valve shall be closed reclaim operation is effective Open EXV 13 33 as avoid low saturated suction...

Page 53: ...claim setpoint 8 3 deg C and all fans are ON provided that fans staging is not enough to avoid the risk of exceeding high pressure override threshold When turning ON the remained condenser hr_val_a is...

Page 54: ...while the master slave function is active then the slave chiller shall be stopped The master slave linkage shall not be allowed to operate if any one of the slave chiller CTRL_PNT DEM_LIM LAG_LIM CTR...

Page 55: ...water flow control is absolutely required on the lag chiller for master slave operations The figures below illustrate master slave application for the most common plant layouts Those figures are not e...

Page 56: ...ical series Master slave chillers dedicated primary pumping constant flow Leaving water control option 4 19 2 Abnormal conditions If a communication failure is detected between the master and the slav...

Page 57: ...r and the slave lwt option the master is configured for lwt control while the slave is configured for ewt control x 6 There is a conflict between the master and the slave lwt option the master is conf...

Page 58: ...ransducer Alarm 23 Compressor A2 Economizer Transducer Alarm 24 Compressor B1 Economizer Transducer Alarm 25 Compressor B2 Economizer Transducer Alarm 26 Circuit A Remote Discharge Pressure Transducer...

Page 59: ...eeze Alarm 75 Cooler Interlock Failure Alarm 76 Condenser Lock Failure Alarm 77 Compressor A1 High Current Alarm 78 Compressor A2 High Current Alarm 79 Compressor B1 High Current Alarm 80 Compressor B...

Page 60: ...oss L3 Alarm 310 Compressor B1 Unbalance 14 Alarm 311 Compressor B1 Unbalance 18 Alarm 312 Compressor B1 No Motor Current Alarm 313 Compressor B1 Star Delta Starter Failure Alarm 314 Compressor B1 Con...

Page 61: ...30 GK 30HZ V2 SR 2 2 1 CESRNRCP53 10 NRCP PD4 SLAVE ADDRESS 53 version 1 0 2 CESRSCPM10 60 PD4 SCPM board download SR 1 06 2 1 Software can be downloaded through CCN bus or through SIO bus 2 Software...

Page 62: ...ng means that the unit is started or allowed to start wOff means that the unit is stopped with all its outputs off wStopping means that the unit is required to stop but all its outputs compressors are...

Page 63: ...trol DISPLAY SCREEN TABLE NAME CIRCA_AN PIC TABLE TYPE 11H instance 2 DESCRIPTION STATUS UNITS POINTS FORCEABLE 1 CIRCUIT A ANALOG VALUES 2 3 Percent Total Capacity 0 100 CAPA_T N 4 Discharge Pressure...

Page 64: ..._a3 N 22 Fan Output DO 4 On Off fan_a4 N 23 Fan Output DO 5 On Off fan_a5 N 24 Fan Output DO 6 On Off fan_a6 N 25 Fan Output DO 7 On Off fan_a7 N 26 Fan Output DO 8 On Off fan_a8 N 27 Fan Staging Numb...

Page 65: ...On Off cpb1_ols N 7 Compressor 2 Output On Off CP_B2 N 8 Cp2 Mtr Cool Solenoid 1 On Off cpb2_mc1 N 9 Cp2 Mtr Cool Solenoid 2 On Off cpb2_mc2 N 10 Cp2 Oil Solenoid Out On Off cpb2_ols N 11 Cir B Loader...

Page 66: ...ed and the regular calculation shall be used Forced value and force code shall appear in the OPTIONS Points Display table only if the unit is under CCN control and if CHIL_S_S is disabled If PUMP 1 is...

Page 67: ...nn n F pd_sat_b N 11 HR Cond Valve Position nnn n hr_v_pos N 12 13 RECLAIM DISCRETE PARAM N 14 Heat Reclaim Select Yes No No RECL_SEL N 15 Condenser Flow Status Open Close condflow N 16 Cir A Reclaim...

Page 68: ...r B Yes No Mode 16 N 12 High Pres Override Cir A Yes No Mode 17 N 13 High Pres Override Cir B Yes No Mode 18 N 14 High Current Over Cir A Yes No Mode 19 N 15 High Current Over Cir B Yes No Mode 20 N 1...

Page 69: ...elta T Control 26 3 OAT Control 27 28 Demand Limit Type Select 0 to 2 0 lim_sel 29 0 None 30 1 Switch Control 31 2 0 10vdc Control 32 Vdc For 100 Demand Lim 0 to 10 0 volts lim_mx 33 Vdc For 0 Demand...

Page 70: ...rtday 10 Time 00 00 to 24 00 02 00 starttim 11 Minutes to Add 0 to 1440 60 min_add 12 13 DAYLIGHT SAVINGS STOP 14 Month 1 to 12 10 stopmon 15 Day 1 to 31 15 stopday 16 Time 00 00 to 24 00 02 00 stopti...

Page 71: ...00000000 dow5 15 Occupied From 0 00 24 00 0 00 occtod5 16 Occupied To 0 00 24 00 24 00 unoctod5 17 Period 6 DOW MTWTFSSH 0 1 00000000 dow6 18 Occupied From 0 00 24 00 0 00 occtod6 19 Occupied To 0 00...

Page 72: ...ING 14 Heating Setpoint 80 to 153 100 0 F hsp 15 Voltage No Reset Value 0 to 10 0 0 volts v_hr_no 16 Voltage Full Reset Value 0 to 10 0 0 volts v_hr_fu 17 Delta T No Reset Value 0 to 25 0 0 F dt_hr_no...

Page 73: ...POR PIC TABLE TYPE 12H instance 6 1 PowerDown 1 day mon year nnnnnn ddmmyy date_of1 2 PowerDown 1 hour minute nnnn hhmm time_of1 3 Power On 2 day mon year nnnnnn ddmmyy date_on1 4 Power On 2 hour minu...

Page 74: ...et by default to No for the slave chiller 5 This item is true when chiller has loaded its total unbroken capacity tonnage TABLE NAME SERMAINT PIC TABLE TYPE 12H instance 5 DESCRIPTION STATUS UNITS POI...

Page 75: ...oler Pump 2 Hours nnnnn hours hr_cpum2 16 Condenser Pump Hours nnnnn hours hr_hpump Note Table for display only TABLE NAME MTA_SCHM PIC TABLE TYPE 12H instance 4 DESCRIPTION STATUS DEFAULTUNITS POINT...

Page 76: ...00 to 23 59 ENDTIME 7 Next Occupied Day Mon to Sun NXTOCDAY 8 Next Occupied Time 00 00 to 23 59 NXTOCTIM 9 Next Unocupied Day Mon to Sun NXTUNDAY 10 Next Unoccupied Time 00 00 to 23 59 NXTUNTIM 11 Pr...

Page 77: ...ader 1 output b4 cpa1_ld2 Loader 2 output b5 oilpmp_a Oil pump output circuit A CPA1_MUX all H DO Compressor A1 Command CP_A1 All H DO Condenser Water Pump Command CONDPUMP pump_seq 1 H DO Cooler Wate...

Page 78: ...ooling 1 b1 cpb1_mc2 Motor cooling 2 or economizer valve b2 cpb1_ols Oil solenoid b3 cpb1_ld1 Loader 1 output b4 cpb1_ld2 Loader 2 output b5 oilpmp_b Oil pump output circuit B CPB1_MUX cpb1_mta 0 H DO...

Page 79: ...r Temperature HR_EWT hd_selec 0 H AO 4 20 mA 0 10Vdc Varifan or Water Valve Circuit B HD_B hd_selec 0 H AO 4 20 mA 0 10Vdc Varifan or Water Valve Circuit A HD_A cb2_mta 0 H AI psi Discharge Pressure C...

Page 80: ...output 3 circuit A b3 fan_a4 Fan output 4 circuit A b4 fan_a5 Fan output 5 circuit A b5 fan_a6 Fan output 6 circuit A b6 fan_a7 Fan output 7 circuit A b7 fan_a8 Fan output 8 circuit A b4 fan_b1 Fan o...

Page 81: ...cl_opt yes heat_sel yes heat_sel yes heat_sel yes H DOM NRCP AQUASNAP Basic board multilexed DO s or AUX 1 Basic board multilexed DO s b9b8b7b6b5b4b3b2b1b0 b0 hr_val_a reclaim valve circuit A b1 hr_va...

Page 82: ...l Pressure DOP_A1 S A F Discharge Superheat Circuit B DSH_B S A F Discharge Superheat Circuit A DSH_A S A Percent Active Demand Limit Value DEM_LIM S A F Chiller Control Water CTRL_WT S A F Chille Con...

Page 83: ...er Slave Control on mode off mode unit is commended to OFF or totally failed on mode unit is commended to ON status could also be delay STATE S A F Saturated Suction Temperature Circuit B SST_B S A F...

Page 84: ...bit 0 AO Channel 51 CPA1 OP AI Channel 88 MUX DI 1 Channel 11 HD A AO Channel 50 CPA1 CUR AI Channel 87 EXT VDC AI Channel 10 DO Ch 49 bit 7 CPA1 PUL DO Channel 86 AI Channel 09 DO Ch 49 bit 6 oilpmp...

Page 85: ...nnel 55 CPB1 STA AI Channel 114 CPA1 STA AI Channel 92 lim sw DI 11 bit 3 AI Channel 54 CPB1 TMP AI Channel 113 CPA1 TMP AI Channel 91 hc sw DI 11 bit 2 AI Channel 53 CPB1 DGT AI Channel 112 CPA1 DGT...

Page 86: ...M BOARD Address 117 SCPM BOARD Address 40 pump_def DI 11 bit 7 cond_flow DI 11 bit 6 elec box DI 11 bit 5 AI Chan 115 16 AI Chan 93 94 lock 1 DI 11 bit 4 CPB1 STA AI Channel 114 CPA1 STA AI Channel 92...

Page 87: ...bit 0 AO Channel 51 CPA1 OP AI Channel 88 MUX DI 1 Channel 11 HD A AO Channel 50 CPA1 CUR AI Channel 87 EXT VDC AI Channel 10 DO Ch 49 bit 7 CPA1 PUL DO Channel 86 AI Channel 09 DO Ch 49 bit 6 oilpmp...

Page 88: ...OP AI Channel 88 MUX DI 1 Channel 11 CPA1 CUR AI Channel 87 EXT VDC AI Channel 10 DO Ch 49 bit 7 CPA1 PUL DO Channel 86 AI Channel 09 DO Ch 49 bit 6 oilpmp a DO 85 bit 5 AI Channel 08 DO Ch 49 bit 5...

Page 89: ...Channel 117 CP A2 DO Channel 95 DO Channel 21 CPUMP 2 DO Channel 20 CPUMP 1 DO Channel 19 SCPM BOARD 4 Address 117 SCPM BOARD 2 Address 95 pump_def DI 11 bit 7 cond_flow DI 11 bit 6 AI Channel 116 AI...

Page 90: ...O Channel 19 SCPM BOARD 4 Address 117 SCPM BOARD 2 Address 95 pump_def DI 11 bit 7 cond_flow DI 11 bit 6 AI Channel 116 AI Channel 94 elec box DI 11 bit 5 AI Channel 115 AI Channel 93 lock 1 DI 11 bit...

Page 91: ...3 SCPM BOARD 4 Address 117 SCPM BOARD 2 Address 95 pump_def DI 11 bit 7 fan b3 DO Ch 56 bit 2 cond_flow DI 11 bit 6 fan b2 DO Ch 56 bit 1 AI Channel 116 AI Channel 94 elec box DI 11 bit 5 fan b1 DO Ch...

Page 92: ...l 19 SCPM BOARD 4 Address 117 SCPM BOARD 2 Address 95 pump_def DI 11 bit 7 cond_flow DI 11 bit 6 AI Channel 116 AI Channel 94 elec box DI 11 bit 5 AI Channel 115 AI Channel 93 lock 1 DI 11 bit 4 CPB1...

Page 93: ...bit 3 CPUMP 1 DO Channel 19 fan b2 DO Ch 56 bit 2 SCPM BOARD 4 Address 117 SCPM BOARD 2 Address 95 pump_def DI 11 bit 7 fan b1 DO Ch 56 bit 1 cond_flow DI 11 bit 6 DO Ch 56 bit 0 AI Channel 116 AI Ch...

Page 94: ...CPB2 MUX Channel 118 CPA2 MUX Channel 96 OIL HTRA DO Channel 22 CP B2 DO Channel 117 CP A2 DO Channel 95 DO Channel 21 CPUMP 2 DO Channel 20 CPUMP 1 DO Channel 19 SCPM BOARD 4 Address 117 SCPM BOARD...

Page 95: ...DO Channel 19 DO 68 bit 2 SCPM BOARD 4 Address 117 SCPM BOARD 2 Address 95 pump_def DI 11 bit 7 hr val b DO 68 bit 1 cond_flow DI 11 bit 6 hr val a DO 68 bit 0 AI Channel 116 AI Channel 94 elec box DI...

Page 96: ...it 4 CPUMP 2 DO Channel 20 cond htr DO 68 bit 3 CPUMP 1 DO Channel 19 DO 68 bit 2 SCPM BOARD 4 Address 117 SCPM BOARD 2 Address 95 pump_def DI 11 bit 7 hr val b DO 68 bit 1 cond_flow DI 11 bit 6 hr va...

Page 97: ...CARRIER SA USER S GUIDE FOR 30GX HX PRO_DIALOG 4 V 2 ECG UG 02 002 Rev Original Page 96 98 Downloaded from www Manualslib com manuals search engine...

Page 98: ...m iom alarm codes 401 to 417 index 139 code 401 to 155 code 417 X Active alarm 1 R 41 h29 X Total Number of active alarms R 40 h28 X R X Compressor B2 Hours R 16 h10 X Compressor B1 Hours R 15 h0F X C...

Page 99: ...I FSM FLOTRONIC I 3200 MP 19XL AUTODIAL AUTODIAL GATEWAY GATEWAY MODEM MODEM BUILDING BUILDING SUPERVISOR SUPERVISOR NETWORK SERVICE TOOL PRIMARY CCN BUS GW WSM 39 L CSM GW GW TSM 39 L 39 L DATA COLL...

Page 100: ...7 12 CAPACITY HEATCOOL PUMP 50 0 0 CTRL PNT CTRL WT LIMIT 6 0 6 7 100 CCN LOCAL REMOTE MENU LOCAL CARRIER CONFORT NETWORK OFF OFF COOLER HEATER ACTIVE READY TO START IN XX MIN ON COOLING ON COOL RECL...