The Chiller Controller has the most features of any Sporlan controller. 

It will control one or two Sporlan Electric Expansion Valves, and con-

trols superheat by means of pressure-temperature control. The controller 

controls each valve independently, and the valves may be different sizes, 

i.e. one SEI-2 and one SEH-175. Pressure-temperature superheat control 

for  one  of  four  common  refrigerants  may  be  selected.  Controllers  can 

be ordered configured for R-22, R-134a, R-404A, R-407C and R-507. 

The refrigerant type can be changed in the field by use of the optional 

“Panel Display.” Onboard readouts show actual superheat, superheat set 

point, and valve position. Two push buttons are provided on the board, 

to change the superheat set point, as well as open, close, or position the 

valve. Proportional and Integral set points are also included to change 

responsiveness of the valve.

As illustrated in Figure 1, the controller is provided with hardware and 

input/output  connections  for  a  number  of  user  specified  purposes.  See 

below:

  •

  One or two valve control

  •

  Two pressure inputs (transducer supplied by Sporlan)

  •

  Two digital inputs (from external switches or relays)

  •

  Four temperature inputs (Sporlan supplied surface or air sensors)

  •

  Optional battery backup for onboard time clock and fail-safe

    valve closure

  •

  Two digit LED readout

  •

  One green LED indicator

  •

  One red LED indicator

  •

  Two push buttons for set point, alarm cancellation, etc.

  •

  One 8-position dip switch for addressing, mode selection, etc.

  •

  Two 20 amp, 240 VAC NC/NO relays

  •

  One 5 amp 240 VAC NC/NO relay

  •

  RS 485 port

  •

  Panel Display jack

Please  note  that  although  relays,  etc.  appear  on  the  Chiller  Board, 

standard software does not support those devices. Custom (proprie-

tary) software must be written for anything other than superheat con-

trol. Please contact Sporlan Division of Parker for more information.

INSTALLATION

When handling the boards, electrostatic protection procedures should 

be  followed.  The  installer  should  be  grounded  through  a  ground 

strap.  If  ground  straps  or  other  ESD  protection  is  not  available, 

ONLY

 handle the board by its edges or by the battery holders. 

DO 

NOT  TOUCH  ANY  COMPONENTS  ON  THE  BOARD  EXCEPT 
THE BATTERY HOLDER AND RELAYS.

1.

   The board should be mounted in a dry, protected environment using 

the predrilled mounting holes in each corner. Make sure none of the 

printed circuit paths or components are touching the metal panel or 

any thing else conductive.

2.

   If only one valve is used, connections are to be made to terminal 

block closest to display readout and push buttons 

PB1

 and 

PB2

.

3.

   Controllers are configured for pressure temperature superheat control.

4.

   Connect temperature sensor to 

TS2

. The sensor is not polarized. For 

suction lines 7/8” or less, the sensor should be mounted to the cop-

per suction line after the evaporator, using the furnished clamps. For 

larger lines or steel piping, a “well sensor,” available from Sporlan, 

should be installed.

5.

   The pressure transducer should be mounted on the top of the suction 

line near the temperature sensor location. Transducer connections to 

the board are as follows:

   

• 

The power wire is red and is connected to the 

1+

 terminal.

   

• 

The signal wire is green and is connected to the 

1S

 terminal.

   

• 

The ground wire is black and is connected the 

1-

 terminal.

6. 

  The valve leads are connected to the terminals labeled

 

Valve 1

.

   

• 

The black lead is connected to terminal labeled 

B

 

of

 

Valve 1

.

   

• 

The white lead is connected to terminal labeled 

W

 of 

Valve 1

.

   

• 

The green lead is connected to terminal labeled 

G

 of 

Valve 1

.

   

• 

The red lead is connected to terminal labeled 

R

 of 

Valve 1

.

7. 

 

DI1

 is a digital input used as a pumpdown terminal. A short or 

closed contact from an external relay will close the valve for pump-

down. When the relay opens or the short is removed, the valve will 

return to normal operation.

8.

   If two valves are used the second valve and its temperature sensor, 

pressure transducer, and pumpdown are connected as above. Caution 

should be used on two valve systems to make sure that the sensors are 

connected to the terminal strip used for the valve they are controlling.

   

  The temperature sensor for 

Valve 2

 is connected to 

TS4

 as    

  described above.

   

  The pressure transducer for 

Valve 2

 is connected to 

2+

2S

2- 

 

  as described above.

 

  The valve is connected to terminals labeled 

Valve 2

 as described 

above.

 

  The pumpdown terminal for 

Valve 2

 is labeled 

DI2

. It is con-

nected as described above.

 

  Power is connected to the terminal marked 

24VAC

.

 

Power 

requirements are 24 volts AC at 40 VA. For protection from 

electrical transients, connect one MOV varistor between one 

leg of the input voltage of the 24 VAC transformer and earth 

ground. Connect a second MOV varistor between the other leg of 

the input voltage of the 24 VAC transformer to earth ground. A 

recommended part number for a MOV is Harris Semiconductor 

DI Pumpdown

Terminals

Two 20 ampere

240 VAC

NC/NO relays

One 5 ampere

240 VAC

NC/NO relay

Holders for 

Optional Fail

Safe Batteries

1-

1S

1+

Pressure 

Transducer 

Terminals

Valve 1 

Cable 

Terminals

TS2 Temperature

Sensor

Terminals

TS1

Two Digit

LED Display

Green

Status LED

Two Push

Buttons

PB1

PB2

Red

Status 

LED

RS 485 Post

Panel

Display

Jack

R

G

W

B

24 Volt AC

50/60 Hz.

40 VA Input

C

hiller

 C

ontroller

Installation and Servicing Instructions

Figure 1

Terminals for Valve 1 shown.
Terminals for Valve 2 similar.