15

Three--Minute Minimum On Time

In normal operation, when a stage turns on, it will remain on for a

minimum of three minutes. If the setpoint is changed, this timer is
automatically cancelled, allowing the equipment to turn off

immediately when the demand is removed.

Heat/Cool setpoints (Desired Temperatures)

A minimum difference of 2

_

F / 1.1

_

C (default) is enforced

between heating and cooling desired temperatures. This is done by

allowing one setting to “push” the other to maintain this difference.
This difference is adjustable via the Install/Service menu under

Thermostat Setup.

Temperature Display

The actual temperature displayed is always rounded toward the
setpoint. This is because the system is operating and measuring the

temperature in sixteenths of a degree, but displaying in whole
numbers. The system may be turned off and on within .5

_

F / .3

_

C

of setpoint, but the display may not change. This is by design and

does not indicate a problem with the control.

Auto Changeover

When Auto mode is enabled (factory default) a change from heat

to cool (or vice versa) will not occur until an opposite mode
demand has existed for 30 minutes. If the setpoint is changed, the

30--minute requirement is defeated. This Auto Changeover time is

adjustable via the Install/Service menu under Thermostat Setup.
Range = 5 -- 120 min.

Smart Recovery

With Smart Recovery selected (factory default), transition out of

setback begins 1.5 hours before selected recovery time and
gradually adjusts room temperature so desired temperature will be

achieved at selected recovery time. It operates in both heating and
cooling. This only applies to programmable operation.
For example: Set back temperature in heating is 64

_

F. Smart

Recovery setpoint is 70

_

F at 7:00 a.m. At 5:30 a.m., the control

calculates the required temperature recovery rate (recovery temp --

set back temp or current temp if greater) / 90 minutes. If the current
temp at 5:30 = 66

_

F, the recovery rate = (70 -- 66)

_

F/90 minutes =

0.04

_

per minute. In order to achieve setpoint, the control ramps up

the setpoint 0.04

_

F / minute from 5:30 a.m. until 7:00 a.m.

NOTE

: Temperatures should not be set back so far that the

equipment cannot recover in 90 minutes.

Media Filter

If

MEDIA

or

MEDIA+EAC

is installed in the indoor unit, the

system will perform a static pressure check of the system every 24
hours at 1:00 p.m. to monitor filter accumulation (TrueSense

t

Dirty Filter Detection) or whenever power is applied to the system
or the system is transitioned from Off to Cool or Heat modes. The

blower will run at a medium airflow for one minute.
This system operates by setting a base line static pressure based on

the highest airflow the system could run (this could be heat or cool

airflow.) The measurement is taken at a low airflow and then
calculated up to the highest airflow the system could see.

Frozen Coil Detection

During cooling operation, the User Interface will monitor the static

pressure of the system. If the static pressure is increasing
dramatically, the User Interface will turn off cooling for up to one

hour, record fault in the “Last 10 Events” screen, and run the fan at
a reduced airflow. The User Interface will continue to monitor the

static pressure. If it is reduced before one hour has elapsed, it will

resume cooling operation. After one hour, cooling will be resumed.

Dehumidify Operation

Once a target cooling humidity setpoint is selected in the Advanced

Setup COOLING HUMIDITY screen, two other setup options
affect Dehumidify operation: AC AIRFLOW and DEHUMIDIFY.
AC AIRFLOW: This setting is located in the Furnace or Fan Coil

Setup screens and must be set to

COMFORT

to enable normal

dehumidify operation. If set to EFFICIENCY or MAXIMUM, no
special dehumidify operation will take place during a normal

cooling call. Cooling will only operate to satisfy the space
temperature setpoint.
DEHUMIDIFY: Located in the Cooling Humidity screen of the

Advanced Setup, this option has 2 settings:

ON

and

OFF

.

If DEHUMIDIFY is set to

ON

(factory default), then the cooling

unit will be allowed to overcool the space up to 3

_

F / 1.7

_

C if the

humidity level is above the cooling humidity target setpoint.
The amount of over--cooling allowed varies with the

dehumidification demand, the cooling demand, and the actual
space temperature. More over--cooling is allowed with greater

dehumidification demand.
When the space temperature is at or above 75

_

F / 24

_

C and the

dehumidify demand is high, over--cooling up to 3

_

F / 1.7

_

C

is

allowed. As the space temperature approaches 70

_

F / 21

_

C, less

over--cooling is allowed. At 70

_

F / 21

_

C space temperature, no

more over--cooling is allowed no matter how great the dehumidify
demand. This is done to protect the equipment.
If DEHUMIDIFY is set to

OFF

and AC Airflow is set to

COMFORT

, normal dehumidification mode is enabled. For

normal dehumidification, no over--cooling is allowed when the

cooling humidity is above the target setpoint, but airflow will be
reduced during a normal cooling mode to reduce humidity. The

airflow depends on the amount of dehumidify demand. If AC
Airflow is set to

EFFICIENCY

or

MAXIMUM

, only

Dehumidify (over--cooling to dehumidify) will be performed.

Hybrid Heat Setup / Operation

Furnace Lockout

(

in HYBRID HEAT SETUP menu) is the

outside temperature above which the furnace will not run except

for defrost (otherwise known as the aux heat lockout).

Heat Pump Lockout

— (in HYBRID HEAT SETUP) is the

outside temperature below which the heat pump will not run

(otherwise known as the balance point).
These values can be set identical to each other. If they are not

identical, the system will stage up and down normally from heat
pump to furnace when the outside temperature is between these

settings. The User Interface will not allow the heat pump lockout

setting to be above the furnace lockout setting.
The factory default settings for both of these is NONE (no

lockouts). Even though a heat pump lockout temperature may be
set, the system will still use the furnace in defrost operation, and

may stage back down to heat pump when defrost is completed after

a 2 minute delay.

Hybrid Heat Defrost

— (in HYBRID HEAT SETUP) When the

outdoor unit needs a defrost cycle, the furnace will run during
defrost regardless of lockout temperature, unless told not to in the

Hybrid Heat Setup screen. After defrost, the system may stage

down to heat pump after a 2 minute delay.

CCUI

D

01

--

B

Summary of Contents for Infinity SYSTXCCUID01-B

Page 1: ...ectrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Infinity System Recognize safety information This is th...

Page 2: ...ust comply with national local and state codes Infinity Control Location The Infinity Control User Interface is the command center for the Infinity System It should be located where it is easily acces...

Page 3: ...assembly will mount directly to the wall requiring only a small hole in the wall allowing a four wire connection to pass through NOTE Once Infinity Control is secured to wall with the backplate assem...

Page 4: ...ty Control need not be level to operate properly and mark wall through two mounting holes 5 Drill two 3 16 4 8 mm mounting holes in wall where marked 6 Secure mounting plastic to wall using two screws...

Page 5: ...reen Yellow White Red OAT Optional Remote Room Sensor HUM COM 24V Humidifier Connection S2 S1 A B C D ABCD Connections Communicating AC or HP Green Yellow White Red OAT Sensor Optional Variable Speed...

Page 6: ...tified and the Installer will be asked to select Accessories Proceed to Selecting Accessories NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will di...

Page 7: ...UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipment Summary EQUIPMENT SUMMARY FURNAC...

Page 8: ...perature will be gin flashing 8 Set the cooling temperature using the TEMP button 9 Set the remaining periods by using the SCROLL button to select DAY EVENING and SLEEP 10 Exit the scheduling mode by...

Page 9: ...ing mode Refer to operational information for more detail English Metric Display S _F or _C default _F Reset Factory Defaults Program Schedule S Yes No to reset back to Energy Star default Time and Te...

Page 10: ...f the system When COMFORT is not selected the unit will not run reduced airflows for dehumidifica tion Heat Pump airflow is varied depending on outdoor temperature to maximize comfort S EFFICIENCY fix...

Page 11: ...15 MIN OUTSIDE LOCKOUT TEMPS A07030 Fig 28 Hybrid Heat Setup FURNACE LOCKOUT Temperature above which only the heat pump will operate except for defrost S Default NONE S Available settings NONE thru 55...

Page 12: ...OF MAINTENANCE EVERY 12 MONTHS USED 50 RESET A07033 Fig 30 System Maintenance Pressing the right side button will reset the timer Pop up confirmation will be shown Setup Utility Saver Cooling Heat Pu...

Page 13: ...tus The Status screens will show all of the current operating parameters of each installed piece of equipment NOTE To view a less detailed Equipment Status screen press and hold the right side button...

Page 14: ...TION Continuous Fan Operation Pressing FAN button will scroll through the following S AUTO No fan operation except during equipment op eration S LOW Approximately 50 of High Speed operation S MED Half...

Page 15: ...Events screen and run the fan at a reduced airflow The User Interface will continue to monitor the static pressure If it is reduced before one hour has elapsed it will resume cooling operation After...

Page 16: ...or unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage communicating...

Page 17: ...only is active Code 41 Blower Motor Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system...