background image

5

9. Push any excess wire into the wall. Seal hole in wall to pre-

vent any air leaks. Leaks can affect operation.

10. Attach Infinity Control to the mounting plastic by lining up

the plastic guides on the back of the control with the open-
ing on the mounting plastic and push on.

11. Perform installation of all other system equipment (i.e.

dampers, humidifier, ventilator, UV lights, etc.)

12. Turn on power to equipment.

See wiring diagram, Fig. 12, which includes an indoor

communicating furnace or FE fan coil, with a communicating
outdoor unit. No additional OAT (outdoor air temperature) sensor

is required because the Infinity Control will use the temperature
sensor inside the outdoor unit.
See wiring diagram, Fig. 13, for connecting an indoor

communicating furnace or FE fan coil with a 1--stage air
conditioning unit (non--communicating outdoor). An Outdoor Air

Temperature (OAT) sensor may be installed (but is not required) at
the indoor furnace or fan coil OAT terminals. When OAT sensor is

applied, the Infinity System will provide enhanced system features
and benefits.
See wiring diagram, Fig. 13, for connecting an FE fan coil with a

1--stage heat pump (non--communicating outdoor unit). When
OAT is applied, the Infinity System will provide enhanced system

features and benefits.

NOTE

: For other applications not listed, refer to the Network

Interface Module (NIM) Installation Instructions.

A

B

C

D

A

B

C

D

User Interface

Green

Yellow

White

Red

OAT

Optional Remote

Room Sensor

HUM

COM
24V

Humidifier

Connection

S2

S1

A

B

C

D

ABCD

Connections

Communicating

 AC or HP

Green

Yellow

White

Red

OAT

Sensor

(Optional)

Variable-Speed

Furnace/ Fan Coil

A03146

Fig. 12 -- Universal Four--Wire Connection Diagram

A

B

C

D

A

B

C

D

C

Y

ABCD

Connection

User Interface

           1-Spd. 
Non-Communicating
              AC

 

Green

Yellow

White

Red

Optional Remote

Room Sensor

HUM

COM

24V

Humidifier

Connection

   Y/Y2

S2

S1

OAT

OAT

Sensor

Variable-Speed

Furnace/Fan Coil

A07022

Fig. 13 -- Connection Diagram for Furnace or FE Fan Coil

w/1--Stage AC

A

B

C

D

A

B

C

D

ABCD

Connection

User Interface

            1-Spd. 
Non-communicating
               HP

Green

Yellow

White

Red

Optional Remote

Room Sensor

HUM

C

Humidifier

Connection

   Y

S2

S1

W2

 Y

O

C

R

O

R

W

OAT

OAT

Sensor

Variable-Speed

Fan Coil

G

A07023

Fig. 14 -- Connection Diagram for FE Fan Coil with

Non-- Communicating 1--stage HP

Humidifier Connection

A 24VAC bypass or fan powered humidifier may be installed.

NOTE

:

Do Not Use

a traditional humidistat to control humidifier

operation. If a humidifier is installed, let the Infinity Control
operate humidifier.

Bypass Humidifiers

A bypass humidifier should be wired directly to the furnace or fan
coil HUM and 24VAC COM terminals. The Infinity Control will

automatically energize the HUM output during a call for
humidification.

Fan Powered Humidifiers

Most fan powered humidifiers produce internal 24VAC in order to

energize upon a switch or contact closure. For this application, a
24VAC N.O. Isolation Relay (DPST)

MUST

be used to prevent

mixing the internal humidifier power with the indoor equipment

CCUI

D

01

--

B

Summary of Contents for Infinity SYSTXCCUID01-B

Page 1: ...ectrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Infinity System Recognize safety information This is th...

Page 2: ...ust comply with national local and state codes Infinity Control Location The Infinity Control User Interface is the command center for the Infinity System It should be located where it is easily acces...

Page 3: ...assembly will mount directly to the wall requiring only a small hole in the wall allowing a four wire connection to pass through NOTE Once Infinity Control is secured to wall with the backplate assem...

Page 4: ...ty Control need not be level to operate properly and mark wall through two mounting holes 5 Drill two 3 16 4 8 mm mounting holes in wall where marked 6 Secure mounting plastic to wall using two screws...

Page 5: ...reen Yellow White Red OAT Optional Remote Room Sensor HUM COM 24V Humidifier Connection S2 S1 A B C D ABCD Connections Communicating AC or HP Green Yellow White Red OAT Sensor Optional Variable Speed...

Page 6: ...tified and the Installer will be asked to select Accessories Proceed to Selecting Accessories NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will di...

Page 7: ...UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipment Summary EQUIPMENT SUMMARY FURNAC...

Page 8: ...perature will be gin flashing 8 Set the cooling temperature using the TEMP button 9 Set the remaining periods by using the SCROLL button to select DAY EVENING and SLEEP 10 Exit the scheduling mode by...

Page 9: ...ing mode Refer to operational information for more detail English Metric Display S _F or _C default _F Reset Factory Defaults Program Schedule S Yes No to reset back to Energy Star default Time and Te...

Page 10: ...f the system When COMFORT is not selected the unit will not run reduced airflows for dehumidifica tion Heat Pump airflow is varied depending on outdoor temperature to maximize comfort S EFFICIENCY fix...

Page 11: ...15 MIN OUTSIDE LOCKOUT TEMPS A07030 Fig 28 Hybrid Heat Setup FURNACE LOCKOUT Temperature above which only the heat pump will operate except for defrost S Default NONE S Available settings NONE thru 55...

Page 12: ...OF MAINTENANCE EVERY 12 MONTHS USED 50 RESET A07033 Fig 30 System Maintenance Pressing the right side button will reset the timer Pop up confirmation will be shown Setup Utility Saver Cooling Heat Pu...

Page 13: ...tus The Status screens will show all of the current operating parameters of each installed piece of equipment NOTE To view a less detailed Equipment Status screen press and hold the right side button...

Page 14: ...TION Continuous Fan Operation Pressing FAN button will scroll through the following S AUTO No fan operation except during equipment op eration S LOW Approximately 50 of High Speed operation S MED Half...

Page 15: ...Events screen and run the fan at a reduced airflow The User Interface will continue to monitor the static pressure If it is reduced before one hour has elapsed it will resume cooling operation After...

Page 16: ...or unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage communicating...

Page 17: ...only is active Code 41 Blower Motor Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system...

Page 18: ...Morris St S Indianapolis IN 46231 Printed in China Edition Date 03 07 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No...

Reviews: