Checkout -- Heat Pump Heating

S

HIGH HEAT RUNTIME: 5 min.

S

LOW HEAT RUNTIME: 5 min.

S

DEFROST: NO

The heat pump heating mode can be exercised with this menu

option. With a 2--stage heat pump, a low heat runtime and a high
heat runtime are independently selectable to exercise. A defrost

cycle is also selectable. Default time = Fixed 5 min. minimum,

range = 5 -- 120 min.

NOTE

:

Airflows during Checkout modes are fixed to the

Efficiency setting and are independent of other airflow settings. To
view airflows for normal heat pump heating mode, exit the
Checkout screen and apply a heating demand to the system.

Checkout -- Heat Pump Cooling or AC Cooling

S

HIGH COOL RUNTIME: 5 min.

S

LOW COOL RUNTIME: 5 min.

The heat pump cooling mode (or AC cooling mode) can be

exercised with this menu option. With a 2--stage heat pump or AC

unit, a low cool runtime and a high cool runtime are independently
selectable to exercise. The display will change to show the heat

pump or AC operating status.
Default time = Fixed 5 min. minimum, range = 5 -- 120 min.

NOTE

:

Airflows during Checkout modes are fixed to the

Efficiency setting and are independent of other airflow settings. To
view airflows for normal heat pump heating mode, exit the
Checkout screen and apply a heating demand to the system.

Checkout -- Humidifier

S

OFF

S

ON

The humidifier can be exercised On and Off with this menu option.

Checkout -- Ventilator

Speed:

S

OFF

S

LOW

S

HIGH

The ventilator can be exercised through all of its operating speeds
with this menu option.

Checkout -- System Access Module (SAM)

See System Access Module Installation Instructions for full details.

SERVICE MENUS

The Service Info menu will only show the equipment installed in
the system. Below is a sample using a furnace and a heat pump

(Hybrid Heat). A sample service menu is shown in Fig. 32.

SERVICE INFO

FURNACE STATUS

HEAT PUMP STATUS

LAST 10 SYSTEM FAULTS

RUN/FAULT HISTORY

TODAY’S DATE

MODEL/SERIAL NUMBER

SERVICE PHONE NUMBER

   BACK               SELECT

A03205

Fig. 32 -- Service Info Menu

Service -- Furnace Status or Gas PAC Status

The Status screens will show all of the current operating parameters
of each installed piece of equipment.

NOTE

: To view a less detailed Equipment Status screen, press and

hold the right side button for 3 seconds. This will display
equipment stage, fan status, actual and target humidify settings.

Heat Stage:

S

OFF, LOW, HIGH

Displays stage of heat that the furnace is currently delivering.

Airflow CFM:

S

(furnace model dependent)

Cubic Feet per Minute of air the blower is currently delivering.

Inducer RPM (90% furnaces only):

S

Inducer motor RPM value.

Blower RPM:

S

Actual RPM feedback from indoor blower motor.

Static Press:

S

Inches of water. Displays the calculated static pressure

that the fan coil is currently experiencing.

S

If static pressure cannot be accurately calculated, the dis-
play will read UNKNOWN. When this is seen, the sys-

tem is adjusting to high static pressure by cutting back
blower RPM.

Lockout Timer:

S

Seconds

If a lockout timer is active, this will show the current time value.

See furnace manual for details on lockout timers.

Service -- Fan Coil Status

Electric Heat:

S

OFF, LOW, MED, HIGH

Displays stages of electric heat that the fan coil is currently
delivering.

Airflow CFM:

S

(fan coil model number dependent)

Cubic Feet per Minute of air the User Interface is currently
requesting.

Blower RPM:

S

Actual blower motor RPM value

Static Press:

S

Inches of water. Displays the calculated static pressure
that the fan coil is currently experiencing.

S

If static pressure cannot be accurately calculated, the dis-
play will read UNKNOWN. When this is seen, the sys-
tem is adjusting to high static pressure by cutting back

blower RPM.

Service -- Heat Pump / AC Status

Stage: (Heat / Cool)

S

OFF, LOW, HIGH

Displays stage of heating or cooling that the Heat Pump/AC is

delivering.

Defrost:

S

NO, YES

Displays status of defrost mode if heat pump.

Airflow CFM:

S

Airflow User Interface is requesting from blower.

Outdoor Coil Temp:

S

_

F or

_

C (default =

_

F)

Temperature of the outdoor unit coil (only available on 2--stage

communicating outdoor units).

Blower RPM:

S

Actual RPM feedback from indoor motor.

Static Press:

S

Inches of water. Displays the calculated static pressure

that the fan coil is currently experiencing.

CCUI

D

01

--

B

Summary of Contents for Infinity SYSTXCCUID01-B

Page 1: ...ectrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Infinity System Recognize safety information This is th...

Page 2: ...ust comply with national local and state codes Infinity Control Location The Infinity Control User Interface is the command center for the Infinity System It should be located where it is easily acces...

Page 3: ...assembly will mount directly to the wall requiring only a small hole in the wall allowing a four wire connection to pass through NOTE Once Infinity Control is secured to wall with the backplate assem...

Page 4: ...ty Control need not be level to operate properly and mark wall through two mounting holes 5 Drill two 3 16 4 8 mm mounting holes in wall where marked 6 Secure mounting plastic to wall using two screws...

Page 5: ...reen Yellow White Red OAT Optional Remote Room Sensor HUM COM 24V Humidifier Connection S2 S1 A B C D ABCD Connections Communicating AC or HP Green Yellow White Red OAT Sensor Optional Variable Speed...

Page 6: ...tified and the Installer will be asked to select Accessories Proceed to Selecting Accessories NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will di...

Page 7: ...UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipment Summary EQUIPMENT SUMMARY FURNAC...

Page 8: ...perature will be gin flashing 8 Set the cooling temperature using the TEMP button 9 Set the remaining periods by using the SCROLL button to select DAY EVENING and SLEEP 10 Exit the scheduling mode by...

Page 9: ...ing mode Refer to operational information for more detail English Metric Display S _F or _C default _F Reset Factory Defaults Program Schedule S Yes No to reset back to Energy Star default Time and Te...

Page 10: ...f the system When COMFORT is not selected the unit will not run reduced airflows for dehumidifica tion Heat Pump airflow is varied depending on outdoor temperature to maximize comfort S EFFICIENCY fix...

Page 11: ...15 MIN OUTSIDE LOCKOUT TEMPS A07030 Fig 28 Hybrid Heat Setup FURNACE LOCKOUT Temperature above which only the heat pump will operate except for defrost S Default NONE S Available settings NONE thru 55...

Page 12: ...OF MAINTENANCE EVERY 12 MONTHS USED 50 RESET A07033 Fig 30 System Maintenance Pressing the right side button will reset the timer Pop up confirmation will be shown Setup Utility Saver Cooling Heat Pu...

Page 13: ...tus The Status screens will show all of the current operating parameters of each installed piece of equipment NOTE To view a less detailed Equipment Status screen press and hold the right side button...

Page 14: ...TION Continuous Fan Operation Pressing FAN button will scroll through the following S AUTO No fan operation except during equipment op eration S LOW Approximately 50 of High Speed operation S MED Half...

Page 15: ...Events screen and run the fan at a reduced airflow The User Interface will continue to monitor the static pressure If it is reduced before one hour has elapsed it will resume cooling operation After...

Page 16: ...or unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage communicating...

Page 17: ...only is active Code 41 Blower Motor Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system...