![Carrier Infinity SYSTXCCUID01-B Installation Instructions Manual Download Page 12](http://html1.mh-extra.com/html/carrier/infinity-systxccuid01-b/infinity-systxccuid01-b_installation-instructions-manual_2562396012.webp)
12
BLOWER ON DELAY -- Time after hot water is requested that the
blower will turn on.
S
Available settings -- 0 to 240 seconds in 30 second incre-
ments
S
Default is 30
BLOWER OFF DELAY-- Time after hot water request terminates
before the blower will turn off.
S
Available settings -- 0 to 240 seconds in 30 second incre-
ments
S
Default is 0.
Setup -- Accessories
Filter Type:
S
MEDIA (i.e. TrueSense
t
)
S
EAC
S
MEDIA+EAC (i.e. TrueSense
t
)
CLEAN INTERVAL: 30 to 180 days (of actual blower operation).
(Default = 90)
Interval at which the Clean Filter notification will turn on. Applies
to EAC filter selection only.
Humidifier Installed:
S
NO
S
YES
If YES, indicates to the system whether a humidifier is installed
and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months (default=12 months)
Interval at which the Change Humidify Pad notification will be
displayed.
HUMIDIFY WITH FAN:
S
NO (default)
S
YES
If YES, the humidifier will turn on if there is a humidify demand
present. The fan will turn on to Low speed if the fan setting is
Auto.
Ventilator:
NOTE
: Only appears if ventilator is installed.
CLEAN INTERVAL:
S
60 to 180 days of actual operation (default=90)
Interval at which the Clean Ventilator Pre--filter notification will
turn on.
UV Lights Installed
S
NO
S
YES
If YES, indicates to the system whether UV lights are installed.
CHANGE INTERVAL:
S
6 to 48 months operation time (default=12 months)
Interval at which the Change UV Lights notification will be
displayed.
Setup -- System Maintenance
Remind Owner of Routine Maintenance Every:
This setup is used to adjust the timer interval in which the normal
System Maintenance notification is turned on for the homeowner.
(See Fig. 30.)
Range =
S
OFF
S
6 to 24 months, (default=12 months)
SYSTEM MAINTENANCE
< BACK
REMIND OWNER OF
MAINTENANCE EVERY:
12 MONTHS
% USED:
50%
RESET >
A07033
Fig. 30 -- System Maintenance
Pressing the right side button will reset the timer. Pop--up
confirmation will be shown.
Setup -- Utility Saver
Cooling/Heat Pump Heating:
S
Turn off, Low Stage
This setup is available only if the equipment has a utility saver
input (refer to equipment Installation Instructions.) This setup
controls the response of the equipment when the utility saver input
is active.
The choices include:
S
Turn Off , (equipment turns off)
S
Low Stage (available if the AC/heat pump is a 2--stage
model, runs low speed only)
CHECKOUT MENUS
The Checkout menu will show the equipment installed in the
system. A sample checkout menu is shown in Fig. 31.
CHECKOUT
FURNACE
HEAT PUMP HEATING
HEAT PUMP COOLING
HUMIDIFIER
VENTILATOR
BACK SELECT
A03204
Fig. 31 -- Checkout Menu
Checkout -- Furnace or Gas PAC
Make sure the furnace is properly installed before continuing.
S
LOW HEAT RUNTIME: 5 min.
S
HIGH HEAT RUNTIME: 5 min.
This menu item allows the furnace to be exercised. First, a low heat
runtime and high heat runtime are selected. Range = 5 -- 120 min.
If only the low heat is to be exercised:
The furnace will execute its ignition start--up sequence. This
sequence will be displayed on the Infinity Control screen. After the
gas valve and blower motor turn on, the screen will automatically
change to “
FURNACE CHECK
” and show the current operating
status of the furnace.
Checkout -- Electric Heat
S
ELECTRIC HEAT RUNTIME: 5 min., Default time = 5
min., Range = 0 -- 120 min.
If you have a fan coil with electric heaters, this menu item will
allow the heaters to be exercised.
With self--identifying electric heaters, three stages of electric heat
are available to be exercised in any combination. Non--identifying
heaters will only provide one stage of heat.
Enter the run time (in minutes) of each stage of heat to be exercised
then press START (right--side button). The display will change to
show the fan coil’s operating status.
CCUI
D
01
--
B