background image

3

It is not mandatory that the above color code be used, but each
ABCD connector in the system MUST be wired consistently.

Mounting Infinity Control

There are two options for mounting the Infinity Control to the

wall. First, become familiar with all plastic assembly pieces shown
in Fig. 3 through 10. The User Interface will snap together with

either the Recess Mount or the Surface Mount backplate.

Recess Mount

This provides the thinnest mounting configuration (see Fig. 4). The
backplate containing the recessed terminal block can be mounted

directly to the wall by cutting a hole 1 1/2” (38.1 mm) wide by 2

1/8” (54 mm) high. Mark location and cut hole in wall.

NOTE

: Always ensure the Infinity Control location is acceptable

before cutting any holes in wall.

Surface Mount

This provides surface mounting configuration, which allows use of

a small hole in the wall. A surface mount backplate is supplied (see
Fig. 5). Attach backplate as shown in Fig. 8, and the assembly will

mount directly to the wall requiring only a small hole in the wall
allowing a four wire connection to pass through.

NOTE

:

Once Infinity Control is secured to wall with the

backplate assembly (snapped together), care must be taken not to
bend or break the interlocking tabs when removing. Gently remove
Infinity Control by rocking up/down until interlocking tabs release.

Decorative Backplate

Supplied is a thin decorative backplate (see Fig. 6) to hide any
marks/screw holes left from the previous thermostat. This

decorative backplate (or beauty ring) can be used in either the

recess or surface mount installation by snapping it onto back of
recessed mount backplate or surface mount backplate before

securing to wall. See Fig. 9 and 10 for a larger decorative backplate
P/N SYSTXXOLBP01 (5.75”/146 mm wide x 6”/152 mm high),

which can be ordered separately.

A03185

Fig. 3 -- Infinity

t

Control

A03186

Fig. 4 -- Recessed Mount Backplate

A03187

Fig. 5 -- Surface Mount Backplate

A04017

Fig. 6 -- Thin Decorative Backplate

Recessed terminal

block in wall 1

1

/

2

˝

wide by 2 

1

/

8

˝

 high

Recessed Mount

Interlocking Tabs (4)

A03190

Fig. 7 -- Recessed Mount Assembly

CCUI

D

01

--

B

Summary of Contents for Infinity SYSTXCCUID01-B

Page 1: ...ectrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Infinity System Recognize safety information This is th...

Page 2: ...ust comply with national local and state codes Infinity Control Location The Infinity Control User Interface is the command center for the Infinity System It should be located where it is easily acces...

Page 3: ...assembly will mount directly to the wall requiring only a small hole in the wall allowing a four wire connection to pass through NOTE Once Infinity Control is secured to wall with the backplate assem...

Page 4: ...ty Control need not be level to operate properly and mark wall through two mounting holes 5 Drill two 3 16 4 8 mm mounting holes in wall where marked 6 Secure mounting plastic to wall using two screws...

Page 5: ...reen Yellow White Red OAT Optional Remote Room Sensor HUM COM 24V Humidifier Connection S2 S1 A B C D ABCD Connections Communicating AC or HP Green Yellow White Red OAT Sensor Optional Variable Speed...

Page 6: ...tified and the Installer will be asked to select Accessories Proceed to Selecting Accessories NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will di...

Page 7: ...UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipment Summary EQUIPMENT SUMMARY FURNAC...

Page 8: ...perature will be gin flashing 8 Set the cooling temperature using the TEMP button 9 Set the remaining periods by using the SCROLL button to select DAY EVENING and SLEEP 10 Exit the scheduling mode by...

Page 9: ...ing mode Refer to operational information for more detail English Metric Display S _F or _C default _F Reset Factory Defaults Program Schedule S Yes No to reset back to Energy Star default Time and Te...

Page 10: ...f the system When COMFORT is not selected the unit will not run reduced airflows for dehumidifica tion Heat Pump airflow is varied depending on outdoor temperature to maximize comfort S EFFICIENCY fix...

Page 11: ...15 MIN OUTSIDE LOCKOUT TEMPS A07030 Fig 28 Hybrid Heat Setup FURNACE LOCKOUT Temperature above which only the heat pump will operate except for defrost S Default NONE S Available settings NONE thru 55...

Page 12: ...OF MAINTENANCE EVERY 12 MONTHS USED 50 RESET A07033 Fig 30 System Maintenance Pressing the right side button will reset the timer Pop up confirmation will be shown Setup Utility Saver Cooling Heat Pu...

Page 13: ...tus The Status screens will show all of the current operating parameters of each installed piece of equipment NOTE To view a less detailed Equipment Status screen press and hold the right side button...

Page 14: ...TION Continuous Fan Operation Pressing FAN button will scroll through the following S AUTO No fan operation except during equipment op eration S LOW Approximately 50 of High Speed operation S MED Half...

Page 15: ...Events screen and run the fan at a reduced airflow The User Interface will continue to monitor the static pressure If it is reduced before one hour has elapsed it will resume cooling operation After...

Page 16: ...or unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage communicating...

Page 17: ...only is active Code 41 Blower Motor Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system...

Page 18: ...Morris St S Indianapolis IN 46231 Printed in China Edition Date 03 07 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No...

Reviews: