9

SETUP MENU

This menu has several layers, allowing modification of equipment
settings. No settings will need to be made at equipment (i.e. DIP

switches on a furnace). All configuration settings made effective
from this menu will override equipment configuration made by dip

switches. Fig. 25 shows all the information that can be found in the

SETUP

menu.

SETUP

THERMOSTAT

FURNACE

HEAT PUMP

ACCESSORIES

SYSTEM MAINTENANCE

   BACK               SELECT

A03203

Fig. 25 -- Setup Menu

Setup -- Thermostat

Auto Mode Setup:

S

Enable/Disable Auto Changeover mode (default=En-
able).

S

Auto Changeover Time may be adjusted 5 to 120 min-
utes, (default = 30 minutes).

When Auto mode is enabled (factory default) a change from heat
to cool (or vice versa) will not occur until the current cycle is

satisfied and an opposite mode demand has existed for 30 minutes.
If the setpoint is changed, the 30 minute timer is deleted.

Heat/Cool Deadband:

S

0 to 6

_

F / 0 to 3.3

_

C, (default = 2

_

F / 1.5

_

C)

The minimum difference enforced between heating and cooling
desired temperatures. This can allow one setting to “push” the

other to maintain this difference.

Offsets:

This option allows calibration (or deliberate miscalibration) of the
temperature and humidity sensors. These offsets are added to the

actual temperature/humidity values (defaults=0).

S

Temperature Offset: --5

_

F to +5

_

F (--2.8

_

C to +2.8

_

C)

S

Outside Temp Offset: --5

_

F to +5

_

F (--2.8

_

C to +2.8

_

C)

S

Humidity Offset: --10 to +10%

Cycles Per Hour:

S

Maximum cycles per hour = 4 (default) or 6.

S

Anticipator = 1 to 9 (default=3). This adjusts sensitivity
to temperature changes. 1 = most sensitive, 9 = least sen-
sitive.

S

If space is over--conditioning, increase the anticipator
setting.

S

If space is under--conditioning, decrease the anticipator
setting.

Programming:

S

ON (default)-- allows program schedule to be set by user.

S

OFF -- system becomes non--programmable

S

Periods Per Day = 2 or 4 (default=4)

S

Programmable Fan On/Off (default=Off). If ON is se-
lected, fan can be set to Auto, Low, Med, or High.

Smart Recovery:

S

On or Off (default=On)

Applies to programmable operation only. Will start recovery 90
minutes prior to schedule change in both heating and cooling

mode. Refer to operational information for more detail.

English/Metric Display:

S

_

F or

_

C, (default =

_

F)

Reset Factory Defaults:
Program Schedule:

S

Yes/No to reset back to Energy Star default Time and

Temp schedules.

User Settings:

S

Yes/No to reset the user settings in the Advanced Setup

to factory default settings.

Install Settings:

S

Yes/No to reset install settings in Install/Service menus to

factory default settings.

Last 10 System Events:

S

Yes/No to reset last 10 events under Service Info menu.

Setup -- Furnace

Upon a first time start--up of the Infinity Control, the furnace DIP

switch settings will be copied to the furnace setup menu. Any
changes can then be made from the Infinity Control.

Airflow:

S

COMFORT (default)

S

EFFICIENCY

Selects the airflow of the furnace when heating.

EFFICIENCY

is

the airflow used to meet specified ratings,

COMFORT

is a

decreased airflow used to increase the output air temperature and

provide increased comfort.

AC Airflow:

S

COMFORT (default) -- cooling airflow is varied depend-
ing on humidity and temperature demands settings. This

selection enables the full dehumidify and comfort capa-
bilities of the system. When COMFORT is not selected,

the unit will not run reduced airflows for dehumidifica-
tion.

S

EFFICIENCY -- fixed airflow used to achieve specified

ratings -- no dehumidification airflow reduction. This is
nominally 350 CFM/ton, but will vary if a 2--stage out-

door unit is used.

S

MAXIMUM -- 400 CFM/ton. No dehumidification air-
flow reduction.

Dehum Airflow:

S

NORMAL (factory default) -- When equipment is run-

ning to dehumidify, the airflow is allowed to adjust to a
minimum to satisfy the dehumidification call.

S

HIGH -- Minimum airflow during the dehumidify mode

is increased to reduce duct and register sweating.

Low Heat Rise

S

ON

S

OFF (default)

Set to

ON

if the system contains a bypass humidifier. The

ON

setting will increase the furnace low heat airflow.

Staging

S

SYSTEM (default)

S

LOW

S

HIGH

S

FURNACE

NOTE

: Controls the staging of the furnace. More staging options

will be available if furnace is capable of more stages.

SYSTEM

setting will allow the Infinity Control to determine furnace staging.

LOW

will only run the low stage of furnace heat.

HIGH

will only

run the high stage of furnace heat.

FURNACE

will allow the

furnace algorithm to control staging.

CCUI

D

01

--

B

Summary of Contents for Infinity SYSTXCCUID01-B

Page 1: ...ectrical codes during installation All wiring must conform to local and national electrical codes Improper wiring or installation may damage the Infinity System Recognize safety information This is th...

Page 2: ...ust comply with national local and state codes Infinity Control Location The Infinity Control User Interface is the command center for the Infinity System It should be located where it is easily acces...

Page 3: ...assembly will mount directly to the wall requiring only a small hole in the wall allowing a four wire connection to pass through NOTE Once Infinity Control is secured to wall with the backplate assem...

Page 4: ...ty Control need not be level to operate properly and mark wall through two mounting holes 5 Drill two 3 16 4 8 mm mounting holes in wall where marked 6 Secure mounting plastic to wall using two screws...

Page 5: ...reen Yellow White Red OAT Optional Remote Room Sensor HUM COM 24V Humidifier Connection S2 S1 A B C D ABCD Connections Communicating AC or HP Green Yellow White Red OAT Sensor Optional Variable Speed...

Page 6: ...tified and the Installer will be asked to select Accessories Proceed to Selecting Accessories NOTE If the variable speed indoor equipment furnace or fan coil cannot be found the User Interface will di...

Page 7: ...UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Equipment Summary EQUIPMENT SUMMARY FURNAC...

Page 8: ...perature will be gin flashing 8 Set the cooling temperature using the TEMP button 9 Set the remaining periods by using the SCROLL button to select DAY EVENING and SLEEP 10 Exit the scheduling mode by...

Page 9: ...ing mode Refer to operational information for more detail English Metric Display S _F or _C default _F Reset Factory Defaults Program Schedule S Yes No to reset back to Energy Star default Time and Te...

Page 10: ...f the system When COMFORT is not selected the unit will not run reduced airflows for dehumidifica tion Heat Pump airflow is varied depending on outdoor temperature to maximize comfort S EFFICIENCY fix...

Page 11: ...15 MIN OUTSIDE LOCKOUT TEMPS A07030 Fig 28 Hybrid Heat Setup FURNACE LOCKOUT Temperature above which only the heat pump will operate except for defrost S Default NONE S Available settings NONE thru 55...

Page 12: ...OF MAINTENANCE EVERY 12 MONTHS USED 50 RESET A07033 Fig 30 System Maintenance Pressing the right side button will reset the timer Pop up confirmation will be shown Setup Utility Saver Cooling Heat Pu...

Page 13: ...tus The Status screens will show all of the current operating parameters of each installed piece of equipment NOTE To view a less detailed Equipment Status screen press and hold the right side button...

Page 14: ...TION Continuous Fan Operation Pressing FAN button will scroll through the following S AUTO No fan operation except during equipment op eration S LOW Approximately 50 of High Speed operation S MED Half...

Page 15: ...Events screen and run the fan at a reduced airflow The User Interface will continue to monitor the static pressure If it is reduced before one hour has elapsed it will resume cooling operation After...

Page 16: ...or unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage communicating...

Page 17: ...only is active Code 41 Blower Motor Fault cooling mode only ventilator humidifier dehumidifier outdoor unit will be turned off Code 45 Control Circuitry Lockout NOTE For codes 13 14 and 21 the system...

Page 18: ...Morris St S Indianapolis IN 46231 Printed in China Edition Date 03 07 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No...

Reviews: