![Carrier ComfortLink HXC076 Controls, Start-Up, Operation, Service, And Troubleshooting Download Page 93](http://html.mh-extra.com/html/carrier/comfortlink-hxc076/comfortlink-hxc076_controls-start-up-operation-service-and-troubleshooting_2562184093.webp)
93
APPENDIX D (cont)
Object Definitions (cont)
30GXN/GXR/HXA/HXC Series 6 with Software Version 1.1 and later
CCN Table
Name
Description
Status
Units
Point
DataPort
DataLink
BAClink
CIRCBDIO
CIRC. B DISCRETE OUTPUTS
Compressor B1 Relay
Compressor B2 Relay
Loader B1 Relay
Loader B2 Relay
Minimum Load Valve
Oil Heater
Motor Cooling B1 Solenoid
Motor Cooling B2 Solenoid
Oil Pump
Oil Solenoid B1
Oil Solenoid B2
CIRC. B DISCRETE INPUTS
Compressor B1 Feedback
Compressor B2 Feedback
Oil Level Switch
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Close/Open
K_B1_RLY
K_B2_RLY
LOADR_B1
LOADR_B2
MLV
OILB_HTR
MTRCL_B1
MTRCL_B2
OILPMP_B
OILSL_B1
OILSL_B2
K_B1_FBK
K_B2_FBK
OILB_SW
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
CIRCB_AN
CIRCUIT B ANALOG VALUES
Percent Total Capacity
Percent Available Cap.
Circuit Running Current
Discharge Pressure
Suction Pressure
Economizer Pressure
Discharge Superheat Temp
Discharge Gas Temp
Discharge Gas Temp – B1
Discharge Gas Temp - B2
Saturated Condensing Tmp
Saturated Suction Temp
EXV% Open
Variable Head Press Pct.
COMP B1 ANALOG VALUES
B1 Oil Pressure Diff.
B1 Oil Pressure
B1 Motor Temperature
Comp B1 Running Current
Comp B1 % Must Trip Amps
COMP B2 ANALOG VALUES
B2 Oil Pressure Diff.
B2 Oil Pressure
B2 Motor Temperature
Comp B2 Running Current
Comp B2 % Must Trip Amps
0 to 100
0 to 100
0 to 1200
nnn.n
nnn.n
nnn.n
snnn.n
nnn.n
nnn.n
nnn.n
snnn.n
snnn.n
0 to 100
0 to 100
nnn.n
nnn.n
nnn.n
0 to 600
0 to 100
nnn.n
nnn.n
nnn.n
0 to 600
0 to 100
%
%
Amps
PSIG (KPA)
PSIG (KPA)
PSIG (KPA)
°F (°C)
°F (°C)
°F (°C)
°F (°C)
°F (°C)
°F (°C)
%
%
PSIG (KPA)
PSIG (KPA)
°F (°C)
Amps
%
PSIG (KPA)
PSIG (KPA)
°F (°C)
Amps
%
CAPB_T
CAPB_A
B_CURR
DP_B
SP_B
ECNP_B
SH_B
DISTMP_B
DISTMPB1
DISTMPB2
TMP_SCTB
TMP_SSTB
EXV_B
VHPB
DOP_B1
OP_B1
TMTR_B1
B1_CURR
B1_MTA
DOP_B2
OP_B2
TMTR_B2
B2_CURR
B2_MTA
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
NA
RO
RO
NA
RO
NA
RO
RO
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
OPTIONS
FANS
Fan 1 Relay *
Fan 2 Relay †
Fan 3 Relay
Fan 4 Relay
UNIT ANALOG VALUES
Cooler Entering Fluid
Cooler Leaving Fluid
Condenser Entering Fluid
Condenser Leaving Fluid
Lead/Lag Leaving Fluid
TEMPERATURE RESET
4-20 mA Reset Signal
Outside Air Temperature
Space Temperature
DEMAND LIMIT
4-20 mA Demand Signal
Demand Limit Switch 1
Demand Limit Switch 2
CCN Loadshed Signal
Off/On
Off/On
Off/On
Off/On
snnn.n
snnn.n
snnn.n
snnn.n
snnn.n
nn.n
snnn.n
snnn.n
nn.n
Off/On
Off/On
0 = Normal
1 = Redline
2 = Loadshed
°F (°C)
°F (°C)
°F (°C)
°F (°C)
°F (°C)
mA
°F (°C)
°F (°C)
mA
FAN_1
FAN_2
FAN_3
FAN_4
COOL_EWT
COOL_LWT
COND_EWT
COND_LWT
DUAL_LWT
RST_MA
OAT
SPT
LMT_MA
DMD_SW1
DMD_SW2
DL_STAT
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RW
RW
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
NA
RO
NA
NA
RO
NA
NA
RO