APPENDIX G (cont)
SETPOINT: Configuration
UNIT: Base Unit Configuration
*See Table 7.
†See Appendix A.
SERVICE: Configuration
* GXN,R, = 152 F, HXA = 145 F, HXC = 118 F
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
COOLING
Cool Setpoint 1
–20 to 70
44.0
°
F
CSP1
Cool Setpoint 2
–20 to 70
44.0
°
F
CSP2
Ice Setpoint
–20 to 32
32.0
°
F
CSP3
HEATING
Heat Setpoint 1
80 to 140
100.0
°
F
HSP1
Heat Setpoint 2
80 to 140
100.0
°
F
HSP2
RAMP LOADING
Cooling Ramp Loading
0.2 to 2.0
1.0
CRAMP
Heating Ramp Loading
0.2 to 2.0
1.0
HRAMP
HEAD PRESSURE
Head Pressure Setpoint A
80 to 140
113
°
F
HSP_A
Head Pressure Setpoint B
80 to 140
113
°
F
HSP_B
Approach Setpoint
0.1 to 20.0
3.0
°
F
APRCH_SP
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
Unit Type
1 = Air Cooled
2 = Water Cooled
3 = Split System
4 = Heat Machine
5 = Air Cooled Heat Reclaim
1
UNIT_TYP
Unit Size
76 to 350
76
TONS
SIZE
Circuit A % Capacity
0 to 100
50
%
CIRCACAP
Number Circ A Compressor
1 to 2
1
NUMCA
Number Circ B Compressor
0 to 2
1
NUMCB
Discharge Super. Setpoint
10 to 40
22.0
°
F
DSH_SP
EXV Circ. A Min Position
0 to 100
8.0
%
EXVAMINP
EXV Circ. B Min Position
0 to 100
8.0
%
EXVBMINP
Fan Staging Select
1 to 8
1*
FAN_TYPE
Compr. A1 Must Trip Amps
10 to 560
0†
CA1_MTA
Compr. A2 Must Trip Amps
10 to 560
0†
CA2_MTA
Compr. B1 Must Trip Amps
10 to 560
0†
CB1_MTA
Compr. B2 Must Trip Amps
10 to 560
0†
CB2_MTA
Economized?
No/Yes
Yes
ECON_SEL
Number of Evap. Passes
1 to 4
2
EVAPPASS
Circuit with LWT Sensor
A/B
A
LWTCKT
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
PID GAINS
Head Pressure P Gain
–20.0 to +20.0
1.0
HD_PGAIN
Head Pressure I Gain
–20.0 to +20.0
0.1
HD_IGAIN
Head Pressure D Gain
–20.0 to +20.0
0.0
HD_DGAIN
Water Valve Minimum Pos.
0 to 100
20
%
HD_MIN
MISCELLANEOUS
Motor Temp Setpoint
120.0 to 240.0
200.0
°
F
MTR_T_SP
Brine Freeze Point
–20.0 to 34.0
34.0
°
F
BRN_FRZ
Max. Cond. Temp Setpoint
100 to Default
*
°
F
MCT_SP
EXVA Start Position
0 to 40
20
%
EXVSPOSA
EXVB Start Position
0 to 40
20
%
EXVSPOSB
COMPRESSOR ENABLE
Enable Compressor A1
Enable/Dsable
Enable
ENABLEA1
Enable Compressor A2
Enable/Dsable
Enable
ENABLEA2
Enable Compressor B1
Enable/Dsable
Enable
ENABLEB1
Enable Compressor B2
Enable/Dsable
Enable
ENABLEB2