Table 12
Configuration Mode and Sub-Mode Directory (cont)
SUB-
MODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM
EXPANSION
COMMENT
OPT1
FLUD
X
COOLER FLUID
Default: Water
Water
Medium Temperature Brine
Low Temperature Brine (30HX only)
MLVS
YES/NO
MIN LOAD VALVE SELCT
Minimum Load Valve
HPCT
X
HEAD PRESS CONTROL TYPE
No Control
Air Cooled (30GXN,R, 30HXA default)
Water Cooled (30HXC default)
Common Cond (30HXA Common Condenser)
Ind Cond (30HXA Independent Condenser)
VHPT
X
VAR HEAD PRESSURE SELECT
None (30HX, 30GX No Motormaster)
4-20 mA (2-10 vdc)(30GX with Motormaster)
0-20 mA (0-10 vdc)
20-0 mA (10-0 vdc)
PRTS
YES/NO
PRESSURE TRANSDUCERS
Default: Yes
CPC
ON/OFF
COOLER PUMP CONTROL
Default: Off
CNP.I
ON/OFF
CONDENSER PUMP INTERLOCK
Default: Off
(Does not require condenser pump control)
CNPC
X
CONDENSER PUMP CONTROL
Default: No Control
No Control
On when occupied
On with compressor(s)
CWT.S
YES/NO
CONDENSER FLUID SENSORS
Default: No
EMM
YES/NO
EMM MODULE INSTALLED
OPT2
CTRL
X
CONTROL METHOD
Default: Switch
Switch = Enable/Off/Remote Contact
7 Day Occ = 7 Day Schedule
Occupancy = CCN Occupancy
CCN = CCN Control
CCNA
XXX
CCN ADDRESS
Default: 1
Range: 1 to 239
CCNB
XXX
CCN BUS NUMBER
Default: 0
Range: 0 to 239
BAUD
X
CCN BAUD RATE
Default: 9600
2400
4800
9600
19,200
38,400
LOAD
X
LOADING SEQUENCE SELECT
Default: Equal
Equal
Staged
LLCS
X
LEAD/LAG SEQUENCE SELECT
Default: Automatic
Automatic
Circuit A Leads
Circuit B Leads
CP.SQ
X
COMPRESSOR SEQUENCE
Default: Automatic
Automatic
Compressor 1 Leads
Compressor 2 Leads
LCWT
XX.X
∆
F
HIGH LCW ALERT LIMIT
Default: 60
Range: 2 to 60 F
DELY
XX
MINUTES OFF TIME
Default: 0 Minutes
Range: 0 to 15 Minutes
CLS.C
ENBL/DSBL
CLOSE CONTROL SELECT
Default: Disable
ICE.M
ENBL/DSBL
ICE MODE ENABLE
Default: Disable
C.UNB
XX %
CURRENT UNBALANCE SETPOINT
Default: 15%
Range: 10 to 25%
NO.FL
ENBL/DSBL
ENABLE NO FLOW DETECTION
Default: Enable
W.MSG
ENBL/DSBL
WINTERIZE ALERT CONFIG
Default: Enable
ALR.C
X
ALARM RELAY USAGE
Default: Alarms
Alarms
Alarms Only
Off
ENTER
ENTER