119
APPENDIX G (cont)
RESETCON: Options Configuration
SCHEDOVR: Schedule and Timed Override Configuration
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
COOLING RESET
Cooling Reset Type
0 = No Reset
1 = 4 to 20 mA Input
2 = External Temp — OAT
3 = Return Fluid
4 = External Temp — SPT
0
CRST_TYP
4-20 MA RESET
4-20 — Degrees Reset
–30 to +30
0
^F
C420_DEG
REMOTE RESET
Remote — No Reset Temp
0 to 125
125
dF
CREM_NO
Remote — Full Reset Temp
0 to 125
0
dF
CREM_FUL
Remote — Degrees Reset
–30 to +30
0
^F
CREM_DEG
RETURN TEMPERATURE RESET
Return — No Reset Temp
0 to 30
10
^F
CRTN_NO
Return — Full Reset Temp
0 to 10
0
^F
CRTN_FUL
Return — Degrees Reset
–30 to +30
0
^F
CRTN_DEG
HEATING RESET
Heating Reset Type
0 = No Reset
1 = 4 to 20 mA Input
2 = External Temp — OAT
3 = Return Fluid
4 = External Temp — SPT
0
HRST_TYP
4-20 MA RESET
4-20 — Degrees Reset
–30 to +30
0
^F
H420_DEG
REMOTE RESET
Remote — No Reset Temp
0 to 125
50
dF
HREM_NO
Remote — Full Reset Temp
0 to 125
80
dF
HREM_FUL
Remote — Degrees Reset
–30 to +30
0
^F
HREM_DEG
RETURN TEMPERATURE RESET
Return — No Reset Temp
0 to 10
10
^F
HRTN_NO
Return — Full Reset Temp
0 to 30
0
^F
HRTN_FUL
Return — Degrees Reset
–30 to +30
0
^F
HRTN_DEG
DEMAND LIMIT
Demand Limit Select
0 = None
1 = External Switch Input
2 = 4 to 20 mA Input
3 = Loadshed
0
DMD_CTRL
Demand Limit at 20 mA
0 to 100
100
%
DMT20MA
Loadshed Group Number
0 to 99
0
SHED_NUM
Loadshed Demand Delta
0 to 60
0
%
SHED_DEL
Maximum Loadshed Time
0 to 120
60
min
SHED_TIM
Demand Limit Switch 1
0 to 100
80
%
DLSWSP1
Demand Limit Switch 2
0 to 100
50
%
DLSWSP2
LEAD/LAG
Lead/Lag Chiller Enable
Disable/Enable
Disable
LL_ENA
Master/Slave Select
Slave/Master
Master
MS_SEL
Slave Address
0 to 239
2
SLV_ADDR
Lead/Lag Balance Select
0 = Master Leads
1 = Slave Leads
2 = Automatic
0
LL_BAL
Lead/Lag Balance Delta
40 to 400
168
hours
LL_BAL_D
Lag Start Delay
0 to 30
5
min
LL_DELAY
Parallel Configuration
Yes/No
No
PARALLEL
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
Schedule Number
0 - 99
0
SCHEDNUM
Override Time Limit
0 - 4
0
hours
OTL
Timed Override Hours
0 - 4
0
hours
OVR_EXT
Timed Override
Yes/No
No
TIMEOVER