APPENDIX G (cont)
OPTIONS1: Options Configuration
OPTIONS2: Options Configuration
DESCRIPTION
STATUS
DEFAULT
POINT
Cooler Fluid
1 = Water
2 = Med. Brine
3 = Low Brine
1
FLUIDTYP
Min. Load Valve Select
No/Yes
No
MLV_FLG
Head Press. Control Type
0 = None
1 = Air Cooled
2 = Water Cooled
3 = Common Condenser
4 = Independent Condenser
0
HEAD_TYP
Var Head Pressure Select
0 = None
1 = 4-20 mA
2 = 0-20 mA
3 = 20-0 mA
0
VHPTYPE
Pressure Transducers
No/Yes
Yes
PRESS_TY
Cooler Pump Control
Off/On
Off
CPC
Condenser Pump Interlock
Off/On
Off
CND_LOCK
Condenser Pump Control
0 = Not Controlled
1 = On when STATE is On
2 = On when compressors are On
0
CNPC
Condenser Fluid Sensors
No/Yes
No
CD_TEMP
EMM Module Installed
No/Yes
No
EMM_BRD
DESCRIPTION
STATUS
DEFAULT
UNITS
POINT
Control Method
0 = Switch
1 = 7 day sched.
2 = Occupancy
3 = CCN
0
CONTROL
Loading Sequence Select
1 = Equal loading
2 = Staged loading
1
SEQ_TYPE
Lead/Lag Sequence Select
1 = Automatic
2 = Circuit A leads
3 = Circuit B leads
1
LEAD_TYP
Compressor Sequence
1 = Automatic
2 = Compressor 1 Leads
3 = Compressor 2 Leads
1
COMP_SEQ
Cooling Setpoint Select
0 = Single
1 = Dual, remote switch controlled
2 = Dual, 7 day clock controlled
3 = Dual, CCN occupancy controlled
4 = 4-20 mA input
0
CLSP_TYP
Heating Setpoint Select
0 = Single
1 = Dual, remote switch controlled
2 = Dual, 7 day clock controlled
3 = Dual, CCN occupancy controlled
4 = 4-20 mA input
0
HTSP_TYP
Ramp Load Select
Enable/Disable
Enable
RAMP_EBL
Heat Cool Select
Cool
Cool
HEATCOOL
High LCW Alert Limit
2 to 60
60.0
∆
F
LCW_LMT
Minutes off time
0 to 15
0
min
DELAY
Deadband Multiplier
1.0 to 4.0
2.0
Z_GAIN
Close Control Select
Disable/Enable
Disable
CLS_CTRL
Ice Mode Enable
Disable/Enable
Disable
ICE_CNFG
Current Unbalance SetPnt
10 to 25
10
%
CUR_TRIP
Enable Noflow Detection
Disable/Enable
Enable
NOFLOWEN
Winterize Alert Config
Disable/Enable
Enable
WINTMSC
Alarm Relay Usage
0 = Alerts and Alarms
1 = Alarms Only
2 = Off
0
ALRMCNFG