![Carrier ComfortLink HXC076 Controls, Start-Up, Operation, Service, And Troubleshooting Download Page 23](http://html.mh-extra.com/html/carrier/comfortlink-hxc076/comfortlink-hxc076_controls-start-up-operation-service-and-troubleshooting_2562184023.webp)
23
Table 12
Configuration Mode and Sub-Mode Directory (cont)
SUB-
MODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM
EXPANSION
COMMENT
RSET
CRST
X
COOLING RESET TYPE
Default: No Reset
No Reset
4 to 20 mA Input
Outdoor Air Temperature
Return Fluid
Space Temperature
CRT1
XXX.X °F
NO COOL RESET TEMP
Default: 125 F
Range: 0° to 125 F
For return fluid reset use cooler
∆
T
CRT2
XXX.X °F
FULL COOL RESET TEMP
Default: 0° F
Range: 0° to 125 F
For return fluid reset use cooler
∆
T
DGRC
XX.X
∆
F
DEGREES COOL RESET
Default: 0° F
Range: –30 to 30 F
HRST
X
HEATING RESET TYPE
Default: No Reset
No Reset
4 to 20 mA Input
Outdoor Air Temperature
Return Fluid
Space Temperature
HRT1
XXX.X °F
NO HEAT RESET TEMP
Default: 0° F
Range: 0° to 125 F
HRT2
XXX.X °F
FULL HEAT RESET TEMP
Default: 125 F
Range: 0° to 125 F
DGRH
XX.X
∆
F
DEGREES HEAT RESET
Default: 0° F
Range: –30 to 30 F
DMDC
X
DEMAND LIMIT SELECT
Default: None
None
Switch
4 to 20 mA Input
CCN Loadshed
DM20
XXX %
DEMAND LIMIT AT 20 mA
Default: 100%
Range: 0 to 100%
SHNM
XXX
LOADSHED GROUP NUMBER
Default: 0
Range: 0 to 99
SHDL
XXX %
LOADSHED DEMAND DELTA
Default: 0%
Range: 0 to 60%
SHTM
XXX
MAXIMUM LOADSHED TIME
Default: 60 Minutes
Range: 0 to 120 Minutes
DLS1
XXX %
DEMAND LIMIT SWITCH 1
Default: 80%
Range: 0 to 100%
DLS2
XXX %
DEMAND LIMIT SWITCH 2
Default: 50%
Range: 0 to 100%
LLEN
ENBL/DSBL
LEAD/LAG CHILLER ENABLE
Default: Disable
MSSL
SLVE/MAST
MASTER/SLAVE SELECT
Default: Master
SLVA
XXX
SLAVE ADDRESS
Default: 0
Range: 0 to 239
LLBL
X
LEAD/LAG BALANCE SELECT
Default: Master Leads
Master Leads
Slave Leads
Automatic
LLBD
XXX
LEAD/LAG BALANCE DELTA
Default: 168 hours
Range: 40 to 400 hours
LLDY
XXX
LAG START DELAY
Default: 5 minutes
Range: 0 to 30 minutes
PARA
YES/NO
PARALLEL CONFIGURATION
Default: No (Series Flow)
ENTER