24
Table 12
Configuration Mode and Sub-Mode Directory (cont)
SUB
MODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM
EXPANSION
COMMENT
SLCT
CLSP
X
COOLING SETPOINT SELECT
Default: Single
Single
Dual Switch
Dual 7 day
Dual CCN Occupied
4 to 20 mA Input (requires EMM)
HTSP
X
HEATING SETPOINT SELECT
Default: Single
Single
Dual Switch
Dual 7 day
Dual CCN Occupied
4 to 20 mA Input (requires EMM)
RL.S
ENBL/DSBL
RAMP LOAD SELECT
Default: Enable
CRMP
X.X
COOLING RAMP LOADING
Default: 1.0
Range: 0.2 to 2.0
HRMP
X.X
HEATING RAMP LOADING
Default: 1.0
Range: 0.2 to 2.0
HCSW
COOL/HEAT
HEAT COOL SELECT
Default: Cool
Z.GN
X.X
DEADBAND MULTIPLIER
Default: 2.0
Range: 1.0 to 4.0
BRN.L
YES/NO
HXC BRINE CONFIG LOCK
Default: No
Yes, if brine FIOP is installed (liquid line
solenoid valves).
SERV
H.PGN
XX.X
HEAD PRESSURE P GAIN
Default: 1.0
Range: –20 to 20
H.IGN
XX.X
HEAD PRESSURE I GAIN
Default: 0.1
Range: –20 to 20
H.DGN
XX.X
HEAD PRESSURE D GAIN
Default: 0.0
Range: –20 to 20
H.MIN
XXX.X
WATER VALVE MINIMUM POS.
Default: 20%
Range: 0 to 100%
MT.SP
XXX.X °F
MOTOR TEMP SETPOINT
Default: 200 F (170 F for Brine)
BR.FZ
XXX.X °F
BRINE FREEZE POINT
Default: 34 F
Range: –20 to 34 F
MC.SP
XXX.X °F
MAX. COND. TEMP SETPOINT
Default: 152 F (GXN,R)
145 F (HXA)
118 F (HXC)
Range: 100 F To Default
EX.S.A
XX.X %
EXVA START POSITION
Default: 20 %
Range: 0 T0 40 %
EX.S.B
XX.X %
EXVB START POSITION
Default: 20 %
Range: 0 To 40 %
EN.A1
ENBL/DSBL
ENABLE COMPRESSOR A1
Default: Enable (All)
EN.A2
ENBL/DSBL
ENABLE COMPRESSOR A2
Disable (HX076-186, GXN,R080-178)
Enable (HX206-271, GXN,R204-350)
EN.B1
ENBL/DSBL
ENABLE COMPRESSOR B1
Default: Enable (All)
EN.B2
ENBL/DSBL
ENABLE COMPRESSOR B2
Disable (HX076-271, GXN,R080-268
Enable (GXN,R281-350)
W.DNE
YES/NO
WINTERIZATION PERFORMED
ECON
YES/NO
ECONOMIZED
No (30HX076-146, 30GXN,R080-106,114)
Yes (30HX161-271,30GXN,R108,118-350)
EVPS
X
NUMBER OF EVAP. PASSES
Range: 1 To 4
LWTC
A/B
CIRCUIT WITH LWT SENSOR
According to number of cooler passes.
AP.SP
XXX.X °F
APPROACH SETPOINT
Default: 3.0 F
Range: 0.1 to 20.0 F
BCST
TD.B.C
ON/OFF
CCN TIME/DATE BROADCAST
Default: Off
OAT.B
ON/OFF
CCN OAT BROADCAST
Default: Off
GS.BC
ON/OFF
GLOBAL SCHEDULE BROADCAST
Default: Off
BC.AK
ON/OFF
BROADCAST ACKNOWLEDGER
Default: Off
ENTER
ENTER