Table 27 — Configuring Temperature Reset
Table 28 — Return Water Reset
MODE
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM
EXPANSION
COMMENT
CONFIGURATION
DISP
TEST
ON/OFF
TEST DISPLAY LEDs
UNIT
TYPE
X
UNIT TYPE
OPT1
FLUD
X
COOLER FLUID
OPT2
CTRL
X
CONTROL METHOD
RSET
CRST
X
COOLING RESET TYPE
0 = No Reset
1 = 4 to 20 mA Input (EMM required)
(Connect to EMM J6-2,5)
2 = Outdoor-Air Temperature
(Connect to TB5-7,8)
3 = Return Fluid
4 = Space Temperature
(Connect to TB5-5,6)
CRT1
XXX.X F
NO COOL RESET TEMP
Default: 125 F (51.7 C)
Range: 0° to125 F
Set to 4.0 for CRST= 1
No Cool Reset
∆
T for CRST=3
CRT2
XXX.X F
FULL COOL RESET TEMP
Default: 0° F (–17.8 C)
Range: 0° to 125 F
Set to 20.0 for CRST=1
Full Cool Reset
∆
T for CRST=3
DGRC
XX.X
∆
F
DEGREES COOL RESET
Default: 0° F (0° C)
Range: –30 to 30 F (–16.7 to 16.7 C)
SUB-MODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM
EXPANSION
COMMENT
RSET
CRST
3
COOLING RESET
TYPE
0 = no reset
1 = 4 to 20 mA input
2 = Outdoor air temp
3 = Return Fluid
4 = Space Temperature
CRT1
10.0 F
(5.5 C)
NO COOL RESET
TEMP
Default: 125 F (51.7 C)
Range: 0° to 125 F
CRT2
2.0 F
(1.1 C)
FULL COOL
RESET TEMP
Default: 0° F (–17.8 C)
Range: 0° to 125 F
DGRC
5.0
∆
F
(2.8
∆
C)
DEGREES COOL
RESET
Default: 0°F (0° C)
Range: –30 to 30 F (–16.7 to 16.7 C)
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
LEGEND
Fig. 14 — Cooling Return Water — No Reset
EWT —
Entering Water (Fluid) Temperature
LWT
—
Leaving Water (Fluid) Temperature
LEGEND
LWT —
Leaving Water (Fluid) Temperature
Fig. 15 — Outdoor-Air Temperature Reset