![Carrier ComfortLink HXC076 Controls, Start-Up, Operation, Service, And Troubleshooting Download Page 78](http://html.mh-extra.com/html/carrier/comfortlink-hxc076/comfortlink-hxc076_controls-start-up-operation-service-and-troubleshooting_2562184078.webp)
78
APPENDIX A (cont)
30GXN,R (High Ambient Data [Position 10 in model no. equal to ‘A’, ‘F’, ‘T’, or ‘V’], All Models)
ComfortLink™ Compressor Protection Module Configuration Header Punch-Outs and Must Trip Amps
UNIT
30GXN,R
VOLTS-Hz
PUNCHOUTS
FOR COMP
A1
PUNCHOUTS
FOR COMP
A2
PUNCHOUTS
FOR COMP
B1
PUNCHOUTS
FOR COMP
B2
COMP A1
MUST TRIP
AMPS
SETTING
COMP A2
MUST TRIP
AMPS
SETTING
COMP B1
MUST TRIP
AMPS
SETTING
COMP B2
MUST TRIP
AMPS
SETTING
281
575-60
1,3,4,5,7
1,2,3,7
1,3,4,5,7
1,2,3,7
188
108
188
108
380-60
1,5,8
1,2,6,7
1,5,8
1,2,6,7
286
164
286
164
460-60
1,3,7
1,2,4,6,8
1,3,7
1,2,4,6,8
236
134
236
134
380/415-50
1,6,8
1,2,6,8
1,6,8
1,2,6,8
294
166
294
166
301
575-60
1,3,4,5,7
1,2,4,5
1,3,4,5,7
1,2,4,5
188
128
188
128
380-60
1,5,8
1,3,4,6,7,8
1,5,8
1,3,4,6,7,8
286
194
286
194
460-60
1,3,7
1,2,5
1,3,7
1,2,5
236
160
236
160
380/415-50
1,6,8
1,3,4,7,8
1,6,8
1,3,4,7,8
294
202
294
202
325
575-60
1,3,4,5,7
1,2,5,7,8
1,3,4,5,7
1,2,5,7,8
188
154
188
154
380-60
1,5,8
1,3,7,8
1,5,8
1,3,7,8
286
234
286
234
460-60
1,3,7
1,3,4,6,7,8
1,3,7
1,3,4,6,7,8
236
194
236
194
380/415-50
1,6,8
1,3
1,6,8
1,3
294
240
294
240
350
575-60
1,3,4,5,7
1,3,4,5,7
1,3,4,5,7
1,3,4,5,7
188
188
188
188
380-60
1,5,8
1,5,8
1,5,8
1,5,8
286
286
286
286
460-60
1,3,7
1,3,7
1,3,7
1,3,7
236
236
236
236
380/415-50
1,6,8
1,6,8
1,6,8
1,6,8
294
294
294
294