31
80HMA
All the devices in the system are connected through a
single bus (type RS485) for communication by using the
two wires connected to Rc and Rh connections.
Each board can be connected to every point in the
network.
The communication rate is 38400 bauds.
A unique address is assigned to each communication
&% !
The addresses range between 1 and 213 and will be
assigned to the boards following the below addressing
rules:
-
Factory setup
-
User setup
^ %&&
interfaces have to be associated to the corresponding
boards (master and slaves). The Slave Boards can manage
! $$X %$ '
$$";$|";%,}% $ X
– except for Pool board which needs only one zone to work
and therefore only one NUI is required.
Pictures on the next two pages show two typical
"@ $X@ $
Y"$@
$ % &
to note down all the serial numbers of the boards
and
User Interfaces and their corresponding positions in the
system.
Below is an example table to record the addresses and
serial numbers referred in the below diagrams:
3.3.2 Network Overview
Device
Addressing Range
30AWH Heat Pumps
2 - 9
Comfort Module board
(Master Board)
10
2-Zone Kit/Pool boards
(Slave Boards)
21 - 84
User interfaces
85 - 213
Serial
Number
Address
Device
Notes
(B) nnnnnn
2
Heat Pump
(A) nnnnnn
10
Master Board
Comfort
Module
(C) nnnnnn
85
User Interface
Master NUI 0
(A) nnnnnn
21
Slave Board
2 Zone kit
board
(C) nnnnnn
86
User Interface
NUI 1 Zone 1
(C) nnnnnn
87
User Interface
NUI 2 Zone 2
The positions of serial numbers are shown in below picture:
(A) Comfort Module (Master Board) &
2-Zone Kit / Pool kit (Slave Board)
(B) Heat Pump 30AWH
(C) User interface - NUI -