53
80HMA
73
Delta Domestic
Hot
Water
Temperature
Priority 0.5
Value of Delta from
Par.72 value of
Domestic Hot Water
Temperature for
Priority 0.5 in
Domestic Hot
Water Priority chart
(°C)
Point E
5
15
5
74
Delta Domestic
Hot
Water
Temperature
Priority 1(F in
Domestic Hot
Water Priority
chart)
Value of Delta from
Par.73 value of
Domestic Hot Water
Temperature for
Priority 1 in Domestic
Hot
Water Priority chart (°C)
Point F
5
15
5
75
Delta Room
Setpoint
Priority 0.5
Value of Delta from
Room Setpoint or
Pool Setpoint to have
Priority 0.5 in Room
Comfort Priority chart
(°C)
Point E
1
5
1
76
Delta Room
Setpoint
Priority 1
Value of Delta from
Room Setpoint or
Pool Setpoint to have
Priority 1 in Room
Comfort Priority chart
(°C)
Point E
1
5
1
77
Delta Water
Temperature
for Domestic
Hot Water
ECO mode
When Eco mode
is Active Dry
Contact (DI# to be
#
decrease the Water
! ^!%
by this value (°)
0
10
5
78
Domestic Hot
Water Booster
Force the Domestic Hot
Water Electric Heater to
turn ON till the Domestic
Hot Water Setpoint is
reached.
0. Off
1. On
0
1
0
79
Boiler Delay
Time
Time in minutes to
wait for turning on the
boiler if the Domestic
Hot Water Priority does
not decrease - set 0 to
disable the Boiler
0
180
15
Variable Table
Available on
RANGE
Par.
No.
Name
Description
Comfort
Module
Zone 1
2-Zone Kit
Pool
User
Interface
Heat
Pump
MIN
MAX
DEFAULT
Master
Zone 1
Zone 2
127
Board address
selected
Address of the board for
which the Variable Table
is shown
10
21
21
21/
22
%%,
,%%
0
255
Own
address
22
Virtual zone
selected
Zone for which variable
'& %
board selected (Par.127
board address)
1
1
2
1
1
2
Own zone