27
80HMA
Comfort Module
80HMA
M00
M03
M06
T06
T09
Power supply
Voltage
V
230
400
Frequency
Hz
50
Phases
#
1
3
Operating voltage limits
V
207-253
360 - 400
Board and auxiliary devices power
consumption (max)
kW
1.15
1.15
1.15
1.15
1.15
Boards and auxiliary circuit breaker
protection (not included) (Reference 2 in
5&$
above)
C6
C6
C6
C6
C6
Electric Heater power consumption
kW
0
3
6
6
9
Electric Heater circuit breaker protection
(not included) (Reference 1 in
Power
$
above)
C6
C20
C32
C16
C20
Running current (max)
A
5
18
31
14
18
Main power cable size and wire numbers
mm²
3G x 2.5
3G x 4
3G x 6
5G x 2.5
5G x 4
Communication cable
FROH2R
,%
²
User Interface -NUI- (additional or
remote) cable
FROH2R
4 x 0.75 mm
²
Booster Heater power supply cable
H05VV-F
3G x 2.5 mm
²
Booster Heater activation cable
FROH2R
2 x 1 mm
²
Domestic Hot Water sensor cable
FROH2R
2 x 0.5 mm
²
Remote Outdoor Air Temperature - OAT
sensor cable
FROH2R
2 x 0.5 mm
²
3.2.16 Recommended Wire Sections