52
80HMA
59
Cooling
Climatic Curve
Water setpoint
@ Max.OAT
" &
Climatic Curve: Water
Setpoint at Par.57:
value (°C)
(Point D Climatic
curve 3)
12
4
20
12
60
Cooling
Climatic Curve
Water setpoint
@ Min.OAT
" &
Climatic Curve: Water
Setpoint at Par.58:
value (°C)
(Point C on Climatic
Curve 3)
18
4
20
18
61
Delta Water
Temperature
for
Room ECO
mode
When Eco mode
is Active Dry
Contact (DI# to be
#
- In Cooling mode
increase the Water
! ^!%
- In Heating mode
decrease the Water
! ^!%
by this value (°)
0
10
5
Domestic Hot Water
71
Management
of
Domestic Hot
Water
production
1. System control
(it
needs Domestic Hot
Water Temperature
Sensor installed and
,}
2. System control with
Solar
(it needs DHW-S
~ Sensor installed
Par112.0:1
and Th-S ~ Solar
Thermostat on DI#5-
Par.111.4:1)
3. External control
(it
needs a Th-S Water
Thermostat installed
on DHW -Tank and
/; %>}
1
2
3
72
Domestic
Hot Water
Temperature
Priority 0
Value of DHW
Temperature for
Priority 0 in Domestic
Hot
Water Priority chart (°C)
Point D
40
80
55
Variable Table
Available on
RANGE
Par.
No.
Name
Description
Comfort
Module
Zone 1
2-Zone Kit
Pool
User
Interface
Heat
Pump
MIN
MAX
DEFAULT
Master
Zone 1
Zone 2
127
Board address
selected
Address of the board for
which the Variable Table
is shown
10
21
21
21/
22
%%,
,%%
0
255
Own
address
22
Virtual zone
selected
Zone for which variable
'& %
board selected (Par.127
board address)
1
1
2
1
1
2
Own zone
Summary of Contents for 80HMA-M00