Auxilary Heaters
91
Electrical
Heater Priority
/
?%'+
the same time.
0. All (Back-up and DHW
Heaters)
1. Max 3 Heaters.
Priority on Back-up
Heaters
2. Max 3 Heaters.
Priority on DHW Heaters
3. Max 2 Heaters.
Priority on Back-up
Heaters
4. Max 2 Heaters.
Priority on DHW Heaters
5. Max 1 Heaters.
Priority on Back-up
Heaters
6. Max 1 Heaters.
Priority on DHW Heaters
0
6
0
92
Outdoor Air
Temperature
Threshold
for BackUp
Heaters
Outdoor Air Temperature
threshold to allow the
backup Heaters to turn
ON.
Below this Threshold the
Heaters are allowed to
turn on (°C)
-30
25
4
93
Water
Temperature
Hysteresis
for BackUp
Heaters
Temperature hysteresis
on the water in tank
to turn on the backup
heaters (°C).
If the Water temperature
is below the requested
Setpoint minus this
+&%?
allowed to be turned on
0
10
3
94
Delay for
BackUp
Heaters
Delay to start backup
heaters when the other
conditions request them
(min)
0
60
10
Variable Table
Available on
RANGE
Par.
No.
Name
Description
Comfort
Module
Zone 1
2-Zone Kit
Pool
User
Interface
Heat
Pump
MIN
MAX
DEFAULT
Master
Zone 1
Zone 2
127
Board address
selected
Address of the board for
which the Variable Table
is shown
10
21
21
21/
22
%%,
,%%
0
255
Own
address
22
Virtual zone
selected
Zone for which variable
'& %
board selected (Par.127
board address)
1
1
2
1
1
2
Own zone