Variable Table
LEVEL 1 and 2
11
User
Use Days button
to
select the sub-parameter
L
Home/pool antifreeze
protection
0. Disable 1. Enable
0
1
1
M
Allow user to change
setpoint/schedule
settings for the zone
0. Allowed 1. Not
Allowed
0
1
0
N
Water Pump (if
configured) behaviour
0. Water Pump does not
stop when room/pool
setpoint is reached 1.
Water Pump stops when
room/pool setpoint is
reached
0
1
0
12
Antifreeze
protection
Setpoint
Home/pool antifreeze
protection setpoint (°C)
6
12
6
13
Too Cold
Setpoint
Too Cold Protection
Setpoint (°C)
0
40
15
14
Too Warm
Setpoint
Too Warm Protection
Setpoint (°C)
0
40
30
15
Room
Hysteresis
Hysteresis on Room
Temperature (°C)
0.1
2
0.5
16
Adjust Heating
Climatic Curve
(X in
Climatic curve
3)
Delta Temperature
applied to
the maximum
Temperature of
Heating Climatic Curve
(°C)
-5
5
0
17
Adjust Cooling
Climatic Curve
(Y in
Climatic curve
3)
Delta Temperature
applied to
the minimum
Temperature of
Cooling Climatic Curve
(°C)
-5
5
0
18
Adjust Room
Sensor
Temperature
Delta to apply to Room
Temperature read by
user Interface (°C)
-5
5
0
Available on
RANGE
Par.
No.
Name
Description
Comfort
Module
Zone 1
2-Zone Kit
Pool
User
Interface
Heat
Pump
MIN
MAX
DEFAULT
Master
Zone 1
Zone 2
127
Board address
selected
Address of the board for
which the Variable Table
is shown
10
21
21
21/
22
%%,
,%%
0
255
Own
address
22
Virtual zone
selected
Zone for which variable
'& %
board selected (Par.127
board address)
1
1
2
1
1
2
Own zone