10
80HMA
The factory settings are given below:
Touch ‘N’ Go Buttons
Heat
Cool
Domestic Hot Water
Home
20 °C
24 °C
60 °C
Away
15 °C
28 °C
50 °C
Sleep
18 °C
26 °C
Not available
2.5.3 Schedule Settings
^& >$$! %&&%,%
and P4. Each zone has its own schedule.
^ !|'& }%'
can be changed as required.
Using virtual zoning (only for access level 3 and the Master
}% &$ &&X
the installation.
Note:
Only Hours could be set, Minute cannot be set.
Important:
Even if scheduling functionality is not used on
site, it is mandatory to enter and validate it.
3 Press
to switch between Heating
% &
or Domestic Hot Water
modes (depending on the
access level).
4 Press or
to set the required temperature for
the selected mode.
The triangle icon above the pressed Touch 'N" Go
button
&&
5 Press
again or
to set the new required
temperature for the next setting.
^ { ' %!!>
and 5.
7 Press $
Comfort change mode.
;$%&$$X X '
and repeat the steps (only in case of 2-zones).
Below parameters can be assigned to each period:
: Room temperature (
}% |==##}
: Domestic Hot Water temperature (
}%' |==##}%& |==##}