4–63
T-365
.
Table 4–7 DataCORDER Alarms
To Access: Press ALT. MODE key then ALARM LIST key
CODE NO.
TITLE
DESCRIPTION
dAL70
Recorder Supply Temperature
Out of Range
The supply recorder sensor reading is outside of the range
of -50°C to 70°C (-58°F to +158°F), or the probe check
logic has determined there is a fault with this sensor.
NOTICE
The P5 Pre-trip test must be run to inacti-
vate the alarm.
dAL71
Recorder Return Temperature
Out of Range
The return recorder sensor reading is outside of the range
of -50°C to 70°C (-58°F to +158°F), or the probe check
logic has determined there is a fault with this sensor.
NOTICE
The P5 Pre-trip test must be run to inacti-
vate the alarm.
dAL72-74
USDA Temperatures 1, 2, 3 Out
of Range
The USDA probe temperature reading is outside of -50°C
to 70°C (-58°F to +158°F) range.
dAL75
Cargo Probe 4 Out of Range
The cargo probe temperature reading is outside of -50°C
to 70°C (-58°F to +158°F) range.
dAL76, 77
Future Expansion
These alarms are for future expansion and are not in use
at this time.
dAL78-85
Network Data Point 1 - 8 Out of
Range
The network data point is outside of its specified range.
The DataCORDER is configured by default to record the
supply and return recorder sensors. The DataCORDER
may be configured to record up to eight additional network
data points. An alarm number (AL78 to AL85) is assigned
to each configured point. When an alarm occurs, the Data-
CORDER must be interrogated to identify the data point
assigned. When a humidity sensor is installed, it is usually
assigned to AL78.
dAL86
RTC Battery Low
The real time clock (RTC) backup battery is too low to ad-
equately maintain the RTC reading.
A real time clock failure is critical to the operation of the
unit. If this alarm occurs, replace the RTC battery at the
next available opportunity. After replacing the battery the
following actions are required:
• Update the RTC setting
• Update the unit’s software configuration
• Update the operational software
• Update all user selectable function code settings
(defrost, setpoint, etc)
dAL87
RTC Failure
An invalid time has been detected. Either the DataCORD-
ER run time hour and minute have not changed at the start
of the hour, or the real time clock (RTC) time has gained
or lost more than 2 minutes in the hour. This situation may
be corrected by cycling the power, setting the clock or
meeting the above criteria for an hour.
Summary of Contents for 69NT40-561-300
Page 2: ......
Page 4: ......
Page 10: ......
Page 14: ......
Page 22: ......
Page 34: ......
Page 108: ......
Page 116: ......
Page 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Page 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Page 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Page 168: ......
Page 172: ......
Page 173: ......