T-365
4–46
AL25
CONDENSER IP
Cause:
Condenser fan motor internal protector (IP) is open.
Component
Insufficient Air Flow
Troubleshooting
Shut down unit and check condenser fan for obstructions.
Corrective Action
Remove obstructions.
Component
Condenser Fan Motor
Troubleshooting
Shut down unit, disconnect power, & check Condenser Fan Motor IP
at plug connection pins KB5 & KB3.
Corrective Action
Replace defective condenser fan motor, refer to Condenser Fan Mo-
tor Assembly Service
AL26
ALL SENSORS FAILURE: SUPPLY/RETURN PROBES
Cause:
Sensors out of range.
Component
All sensors detected as out of range
Troubleshooting
Perform Pre-trip P5:
Corrective Action
If P5 passes, no further action is required.
If P5 fails, replace the defective sensor as determined by P5, refer to
TEMPERATURE SENSOR Service
AL27
ANALOG TO DIGITAL ACCURACY FAILURE
Cause:
Controller AD converter faulty.
Component
Controller
Troubleshooting
Power cycle the unit. If the alarm persists, it indicates a defective mi-
croprocessor.
Corrective Action
Replace defective microprocessor, refer to Controller Service
.
Summary of Contents for 69NT40-561-300
Page 2: ......
Page 4: ......
Page 10: ......
Page 14: ......
Page 22: ......
Page 34: ......
Page 108: ......
Page 116: ......
Page 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Page 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Page 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Page 168: ......
Page 172: ......
Page 173: ......