T-365
4–56
P5-1
Supply Probe Test This test if for units equipped with secondary supply probe only.
The temperature difference between primary supply probe and secondary
supply probe is compared.
Test passes if temperature comparison falls within the specified range.
NOTICE
If this test fails, “P5-1” and “FAIL” will be displayed. If both
Probe tests (this and the SUPPLY/RETURN TEST) pass,
because of the multiple tests, the display will read “P 5”
“PASS.”
P5-2
Return Probe Test For units equipped with secondary return probe only.
The temperature difference between return temperature sensor (RTS) and
return temperature sensor (RRS) probe is compared.
Test passes if temperature comparison falls within the specified range.
NOTICE
1. If this test fails, “P5-2” and “FAIL” will be displayed. If both
Probe tests (this test and the SUPPLY/RETURN) pass,
because of the multiple tests, the display will read “P 5,”
“PASS.”
2. The results of Pre-trip tests 5-0, 5-1 and 5-2 will be used to
activate or clear control probe alarms.
P5-3
Evaporator Fan Di-
rection Test
With evaporator fan running on high speed, measure the temperature differ-
ence between the primary supply and primary return probes. Turn the heat-
ers on for 60 seconds then measure the temperature difference between the
primary supply and primary return probes for up to 120 additional seconds.
This is a Pass/Fail test. The test passes if differential of STS is 0.25°C higher
than RTS.
Test P5-0 must pass before this test is run.
P5-7
Primary vs Sec-
ondary Evaporator
Temperature Sen-
sor Test
This is a Pass/Fail test of the primary evaporator temperature sensor (ETS1)
and secondary evaporator temperature sensor (ETS2).
Test passes if secondary evaporator temperature sensor (ETS2) is /
- 0.5°C of the primary evaporator temperature sensor (ETS1).
P5-8
Primary Evapora-
tor Pressure Trans-
ducer Test
This is a Pass/Fail test of the Primary Evaporator Pressure Transducer.
Test passes if suction pressure transducer (SPT) is /- 0 psi of satura-
tion pressure at current evaporator temperature. Also passes if SPT is within
+/- 1 psi of discharge pressure 6 hours after a power interruption.
Test P5-7 must pass before this test is run.
P5-9
Suction (Evapora-
tor) Pressure
Transducer Test
Units equipped with a secondary Evaporator pressure transducer.
Test passes if suction pressure transducer (SPT) is /- 1.5 psi of the
evaporator pressure transducer (EPT).
Test P5-8 must pass before this test is run.
CODE
TITLE
DESCRIPTION
Summary of Contents for 69NT40-561-300
Page 2: ......
Page 4: ......
Page 10: ......
Page 14: ......
Page 22: ......
Page 34: ......
Page 108: ......
Page 116: ......
Page 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Page 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Page 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Page 168: ......
Page 172: ......
Page 173: ......