4–57
T-365
P6 Tests - Refrigerant Probes, Compressor and Refrigerant Valves
: Pass/Fail testing is performed for the
compressor, EEV, DUV, ESV, and the refrigerant pressure and temperature sensors.
P5-10
Humidity Sensor
Controller Configu-
ration Verification
Test
This is a Pass/Fail/Skip test of the humidity sensor configuration.
Test passes if the controller configuration has humidity sensor in.
Test fails if the controller configuration has humidity sensor out and Vout is
greater than 0.20 Volts for the humidity sensor.
Test is skipped if the controller configuration has the humidity sensor out and
Vout is less than 0.20 Volts.
Test P5-9 must pass before this test is run.
P5-11
Humidity Sensor
Installation Verifi-
cation Test
This is a Pass/Fail test of humidity sensor installation (sensor is present).
Test passes if Vout is greater than 0.20 Volts for the humidity sensor.
Test fails if Vout is less than 0.20 Volts for the humidity sensor.
Test P5-10 must pass before this test is run.
P5-12
Humidity Sensor
Range Check Test
This is a Pass/Fail test of the Humidity Sensor Range.
Test passes if Vout for the humidity sensor is between 0.33 Volts and 4 Volts.
Test fails if Vout is outside of this range.
Test P5-11 must pass before this test is run.
CODE
TITLE
DESCRIPTION
P6-0
Discharge Therm-
istor Test
If Alarm 64 is active the test fails. Otherwise, the test passes.
P6-1
Suction Thermis-
tor Test
If the Suction Temperature Sensor (CPSS) both is configured ON and is in-
valid, the test fails. Otherwise the test passes.
P6-2
Discharge Pres-
sure Transducer
Test
If Alarm 65 is active any time during the first 45 second period, the test fails.
Otherwise, the test passes.
P6-3
Suction Pressure
Transducer Test
If Alarm 66 is active the test fails. Otherwise the test passes.
P6-4
Compressor Cur-
rent Draw Test
Compressor current is tested before and 10 seconds after start up. If current
does not increase, the test fails. P6-7 is run at the end of P6-4. If this test fails,
P6-6 is skipped.
P6-5
Compressor Leak
Test
Pre-trip P6-5 ensures that the compressor holds pressure. After compressor
pump up and pump down, the compressor is turned off for 62 seconds. When
suction side pressure holds (less than 8 psi rise) for 10 seconds, P6-5 pass-
es, otherwise the Compressor Leak Test fails.
NOTICE
P6-6 through P6-10 are conducted by changing status of each valve and comparing suction
pressure change and/or compressor current change with predetermined values. Tests will
cause compressor and condenser fans to cycle on and off as needed to generate the pressure
required for individual Pre-trip sub tests. The compressor will start in order to build discharge
pressure, followed by compressor pump down sequence. At the conclusion of compressor
pump down sequence, the compressor will shut down and the valve test will start.
P6-6
Economizer Valve
Test
Passes if suction pressure increases a minimum of 4 psia when the valve
opens for 15 seconds.
CODE
TITLE
DESCRIPTION
Summary of Contents for 69NT40-561-300
Page 2: ......
Page 4: ......
Page 10: ......
Page 14: ......
Page 22: ......
Page 34: ......
Page 108: ......
Page 116: ......
Page 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Page 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Page 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Page 168: ......
Page 172: ......
Page 173: ......