4–47
T-365
AL28
LOW SUCTION PRESSURE
Cause:
Suction pressure too low for normal operation
Component
N/A
Troubleshooting
Power cycle the unit.
Corrective Action
Resetting the unit may correct problem, monitor the unit.
Component
Suction Pressure Transducer (SPT)
Troubleshooting
Confirm accurate SPT pressure readings, refer to MANIFOLD
GAUGE SET
Corrective Action
Replace SPT if defective
Component
Discharge Pressure Transducer (DPT)
Troubleshooting
Confirm accurate DPT pressure readings, refer to MANIFOLD
GAUGE SET
Corrective Action
Replace DPT if defective
AL29
AUTOFRESH FAILURE
Cause:
Alarm 29 is triggered if CO
2
or O
2
level is outside of the limit range and the vent position is at 100%
for longer than 90 minutes.
Component
Alarm LED will be activated and user intervention is required.
Troubleshooting
Refer to eAutoFresh manual.
Corrective Action
The alarm is triggered off when atmospheric conditions are within lim-
it settings.
AL50
AIR VENT POSITION SENSOR (VPS)
Cause:
VPS Sensor out of range.
Component
Vent Position Sensor (VPS)
Troubleshooting
Make sure VPS is secure.
Corrective Action
Manually tighten panel.
Troubleshooting
If the alarm persists, replace the sensor or the assembly.
Corrective Action
Replace VPS.
Summary of Contents for 69NT40-561-300
Page 2: ......
Page 4: ......
Page 10: ......
Page 14: ......
Page 22: ......
Page 34: ......
Page 108: ......
Page 116: ......
Page 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Page 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Page 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Page 168: ......
Page 172: ......
Page 173: ......