4–41
T-365
AL16
COMPRESSOR CURRENT HIGH
Cause:
Compressor current draw is over the calculated maximum for 10 minutes.
Component
Current Sensor
Troubleshooting
Compare Cd3 to actual measured current at wire T1-T2 or T3 going
to the compressor contactor. If there is a difference, determine
whether this is caused by current sensor or amp clamp tool.
Corrective Action
Replace current sensor if defective.
Component
Amperage is indeed too high.
Troubleshooting
Confirm supply voltage/frequency is within specification and bal-
anced according to Electrical Data
.
Corrective Action
Correct power supply.
Component
Operating Conditions
Troubleshooting
Make sure system pressures are relevant to operating conditions.
Corrective Action
Check air flow of condenser.
Check Refrigerant charge, refer to REFRIGERATION SYSTEM
SERVICE
Component
Monitor Unit
Troubleshooting
Alarm is display only the alarm may clear itself during operation
Corrective Action
If alarm remains active or is repetitive replace compressor at next
available opportunity, refer to COMPRESSOR Service