background image

8

3.9 -   Connections at the user terminal block

Connections available at the user terminal block may vary 
depending on the selected options.

Terminal block connections
Description

Board

Input/Output

Connector

Remarks

On/Off switch

SIOB, circuit A

DI-01

J1

Used for the unit on/off control if the unit is in Remote mode

Second setpoint switch

SIOB, circuit A

DI-02

J1

The contact is taken into consideration if the unit is in Remote mode

Demand limit switch 1

SIOB, circuit A

DI-03

J1

Used to control demand limit. See section 7.7

Heat cool select status

SIOB, circuit A

DI-04

J1

Used to select heat cool mode

Condenser flow status (30XW only)

SIOB, circuit A

DI-08

J1

Used to control the condenser status

Setpoint reset control

SIOB, circuit A

AI-10

J9

Allows the customer to reset the currently selected setpoint

Alarm relay

SIOB, circuit A

DO-05

J23

Indicates alarms

Running relay

SIOB, circuit A

DO-06

J22

Indicates if the unit is ready to start or operating

Optional 

Occupancy override

SIOB, EMM

DI-01

J1

Enables to switch between occupied (closed contact) and 

unoccupied mode (open contact)

Demand limit switch 2

SIOB, EMM

DI-02

J1

Used to control demand limit. See section 7.7

Customer interlock 

SIOB, EMM

DI-03

J1

Used for the customer safety loops

Ice done contact 

SIOB, EMM

DI-04

J1

Used to control the setpoint according to the occupancy schedule

Capacity limit control

SIOB, EMM

AI-10

J9

Used for capacity limitation

Chiller partially shutdown

SIOB, EMM

DO-05

J23

Indicates the shutdown of one of the circuits

Chiller shutdown

SIOB, EMM

DO-06

J22

Indicates the unit shutdown

Chiller capacity running output (0 to 10 V)

SIOB, EMM

AO-01

J10

Reports the capacity percentage of the unit

Heat reclaim condenser flow status (30XA only)

SIOB, Heat reclaim DI-01

J1

Used to verify the water flow on the condenser side

Heat reclaim enable switch (30XA only)

SIOB, Heat reclaim DI-02

J1

Used to switch between air-condenser (open contact) and water 

condenser (closed contact) in Remote mode

Free cooling disable switch (30XA only)

SIOB, Free cooling DI-01

J1

Used to control free cooling when the unit is in Remote mode

3.9.2 -  Volt-free contact on/off/cooling/heating

If the unit operates in Remote mode, on/off contacts and 
heating/cooling contacts operate as follows:

Without multiplexing

   

Off

Cooling

Heating

On/Off contact

open

closed

closed

Cooling/heating contact

-

open

closed

With multiplexing

   

Off

Cooling

Heating

Auto

On/Off contact

open

closed

closed

open

Cooling/heating contact

open

open

closed

closed

Legend:

1.   Off: Unit is stopped

2.   Cooling: Unit is allowed to start in Cooling

3.   Heating: Unit is allowed to start in Heating

4.   Auto: Unit can run in Cooling or Heating in accordance with the changeover  

values.

3.9.3 -  Volt-free setpoint selection contact

This dry contact input is used to switch between setpoints. It 
is active only when the control is in Remote mode.

Cooling

   Heating

Setpoint 1 Setpoint 2 Setpoint 1 Setpoint 2

Setpoint selection contact open

closed

open

closed

3.9.1 -  General description

Some contacts can be accessed only when the unit operates 
in Remote mode.

The following table summarises the connections at the user 
terminal block.

3.9.4 -  Volt-free demand limit selection contact

Up to two dry contacts can be used to limit unit capacity. 
Note that the second contact is available for units with the 
energy management module.

Capacity limitation with two contacts is as follows:

100%

Limit 1

Limit 2

Limit 3

Demand limit 1 contact

open

closed

open

closed

Demand limit 2 contact

open

open

closed

closed

The limits are defined in the SETPOINT menu.

Summary of Contents for 30XA-ZE

Page 1: ...CONTROLS MANUAL Operation instructions Original document Touch Pilot Control AquaForce PUREtec with R 1234ze E 30XA XAS XW 30XA ZE XW ZE...

Page 2: ...ace access 13 5 2 Web browser configuration 13 5 3 Technical documentation access 13 6 TOUCH PILOT INTERFACE DETAILS 14 6 1 Menu structure 14 6 2 Detailed menu description 15 6 3 Alarms menu 20 6 4 Co...

Page 3: ...7 21 Dry cooler option 30XW 31 7 22 Hydronic kit option 30XA 31 7 23 30XA ZE and 30XW ZE units HFO 31 7 24 High condensing temperature option 30XW 31 7 25 Maximum condenser leaving water temperature...

Page 4: ...recommended to ensure optimal operation of the equipment as well as the optimization of all available functionalities Note that this document may refer to optional components and certain functions op...

Page 5: ...ames with great care IMPORTANT Some specific safety precautions should be taken in case of HFO units For more information about handling the equipment safely please refer to the IOM Unit documentation...

Page 6: ...the boards otherwise the boards may be damaged In the event of a power supply interrupt the unit restarts automatically without the need for an external command However any faults active when the sup...

Page 7: ...eat reclaim option Suction gas temperature sensor This sensor is used to control the suction gas temperature It is located at the suction line of each compressor Discharge gas temperature sensor Thiss...

Page 8: ...unit Heat reclaim condenser flow status 30XA only SIOB Heat reclaim DI 01 J1 Used to verify the water flow on the condenser side Heat reclaim enable switch 30XA only SIOB Heat reclaim DI 02 J1 Used to...

Page 9: ...Setpoint NOTE The synoptic screen display may vary depending on pumps configuration 4 TOUCH PILOT CONTROL INTERFACE 4 1 General description Touch Pilot includes the 5 in touch screen allowing for easy...

Page 10: ...hutdown by pressing Confirm Stop or return to the previous screen by pressing the Back button Once the unit has been stopped the Synoptic screen will be displayed see also section 4 2 2 Shows the last...

Page 11: ...he necessary changes Press the Up Down buttons to navigate between the screens Once all the necessary modifications have been made press to confirm or to cancel changes 4 4 1 General parameters screen...

Page 12: ...e selected period will be presented in the form of the green band on the timeline Press to confirm or to cancel changes 1 Selection of the applicable days for the time schedule 2 Modification of the p...

Page 13: ...and use a direct connection NOTE Two users can be connected simultaneously with no priority between them The last modification is taken into account 5 3 Technical documentation access When theTouch P...

Page 14: ...14 6 TOUCH PILOT INTERFACE DETAILS 6 1 Menu structure...

Page 15: ...y Running Ready Override Tripout Test Runtest 3 0 to 1 Net Cmd Start Stop Unit start stop via Network 4 0 to 1 Net Cmd Occupied Unit time schedule via Network 5 min Minutes Left for Start Minutes befo...

Page 16: ...conomizer Gas Temp B Economizer gas temperature circuit B 28 C Economizer Gas Temp C Economizer gas temperature circuit C 29 C Dry Cool Leav Water Tmp Dry Cooler Leaving Water Temperature units fitted...

Page 17: ...own Indicator State Shutdown indicator status 21 0 to 100 Cond 3 Way Valve Pos Condenser 3 way valve position 22 off on Cooler Heater Command Evaporator heater command status 23 off on Ready or Runnin...

Page 18: ...s condenser pump 1 12 hour Condenser Pump 2 Hours Operating hours condenser pump 2 not available 13 hour Free Cool A Pump Hours Pump operating hours in Free Cooling circuit A 14 hour Free Cool B Pump...

Page 19: ...lve status circuit B Depends on the selected language English by default FREECOOL Free cooling No Status Unit Displayed text Description 1 GENERAL PARAMETERS GENERAL PARAMETERS 2 0 to 1 Free Cooling D...

Page 20: ...26 6 7 C Cooling Ice Setpoint Ice storage setpoint 4 0 1 to 11 1 0 6 C Cooling Ramp Loading Cooling ramp loading setpoint 5 26 7 to 63 37 8 C Heating Setpoint 1 Heating setpoint 1 6 26 7 to 63 37 8 C...

Page 21: ...6 1 to 15 1 min Unit Off to On Delay Unit Off to On delay 7 00 00 0 Night Mode Start Hour Night mode start time 8 00 00 0 Night Mode End Hour Night mode end time 9 0 to 100 100 Night Capacity Limit N...

Page 22: ...no reset value 8 10 to 51 7 10 C OAT Full Reset Value OAT max reset value 9 0 to 13 9 0 C Delta T No Reset Value Delta T no reset value 10 0 to 13 9 0 C Delta T Full Reset Value Delta T max reset valu...

Page 23: ...ek of the month Depends on the selected language English by default DATETIME Date Time configuration No Status Default Displayed text Description Date DD MM YY 1 1 to 31 Day of month Day of the month...

Page 24: ...en remote off active unoccupied remote off active disabled network off active unoccupied network off active local unoccupied local off active open remote remote off active remote unoccupied remote off...

Page 25: ...vailable the unit is stopped and started again with the second pump If there is no pump available the unit shuts down Units are fitted with the flow switch allowing for the water flow control For more...

Page 26: ...eating setpoint 2 heating auto occupied heating setpoint 1 heating auto unoccupied heating setpoint 2 Any configuration default configuration REMOTE OPERATING TYPE Parameter status Active setpoint Hea...

Page 27: ...dtoprotectthecompressors 7 8 Current limitation Current limitation is used via the demand limit function If the current limitation is active Current Limit Select in the GEN_CONF menu the control calcu...

Page 28: ...units This function determines in which order the circuit capacity is changed Compressor loading is managed by starting stopping the compressors and controlling the position of the slide valve Two ty...

Page 29: ...95 35 0 0 100 100 95 30 0 0 100 100 100 0 0 0 Loading sequence Unloading sequence Lead circ Lag circ 1 Lag circ 2 Lead circ Lag circ 1 Lag circ 2 0 0 0 100 100 100 30 0 0 100 100 95 35 0 0 100 100 90...

Page 30: ...he contact is closed the unit enters the ice storage mode Space temperature AI 01 J25 Analogue input Active setpoint reset via space temperature control Capacity limit control AI 10 J9 Analogue input...

Page 31: ...g Full Load Timeout when the water temperature setpoint is not reached Full Load Timeout GEN_CONF General Configuration 7 21 Dry cooler option 30XW 30XW units may come with the dry cooler option that...

Page 32: ...6 holiday periods Each period is defined by three parameters the month the start day and the duration of the holiday period During the holiday periods the controller will be in occupied or unoccupied...

Page 33: ...ight part of the screen and then select Current Alarms 8 4 Resetting alarms Touch Pilot control distinguishes between two types of alarms General alarms are used to indicate pumps failure transducers...

Page 34: ...ove As above As above 24 15026 Economizer gas thermistor fault circuit C As above As above As above 25 15030 Free cooling liquid thermistor fault circuit A As above Free cooling disabled As above 26 1...

Page 35: ...ump is running Discharge pressure transducer defective refrigerant leak or low condenser water temperature 80 10003 Condenser frost protection circuit B As above Circuit B shuts down but the pump is r...

Page 36: ...uit A Manual None Defective or incorrectly wired solenoid valves defective current transformer 132 10088 Slide valve control unverifiable circuit B Manual None As above 133 10089 Slide valve control u...

Page 37: ...temperature and the VFD fan 67 Alarm Option configuration has changed Contact Carrier Service 68 Alarm Emergency stop Contact Carrier Service 71 Alarm PTC 1 emergency stop Contact Carrier Service 72 A...

Page 38: ...rvice 8 Alert DC undervoltage Contact Carrier Service 9 Alert Inverter overloaded Check the VFD output current 10 Alert Motor overtemperature Check the motor temperature 11 Alert Motor thermistor Cont...

Page 39: ...No 13453 07 2016 Supersedes order No 13453 03 2016 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Reviews: