TEMP – Temperatures
No.
Status
Unit
Displayed text*
Description
1
-
°C
Cooler Entering Fluid
Evaporator entering water temperature
2
-
°C
Cooler Leaving Fluid
Evaporator leaving water temperature
3
-
°C
Condenser Entering Fluid
Condenser entering water temperature
4
-
°C
Condenser Leaving Fluid
Condenser leaving water temperature
5
-
°C
Saturated Cond Tmp cir A
Saturated condensing temperature, circuit A
6
-
°C
Saturated Suction Temp A
Saturated suction temperature, circuit A
7
-
°C
Compressor Suction Tmp A
Compressor suction temperature, circuit A
8
-
°C
Discharge Gas Temp cir A
Discharge gas temperature, circuit A
9
-
°C
Motor Temperature cir A
Motor temperature, circuit A
10
-
°C
Saturated Cond Tmp cir B
Saturated condensing temperature, circuit B
11
-
°C
Saturated Suction Temp B
Saturated suction temperature, circuit B
12
-
°C
Compressor Suction Tmp B
Compressor suction temperature, circuit B
13
-
°C
Discharge Gas Temp cir B
Discharge gas temperature, circuit B
14
-
°C
Motor Temperature cir B
Motor temperature, circuit B
15
-
°C
Saturated Cond Tmp cir C
Saturated condensing temperature, circuit C
16
-
°C
Saturated Suction Temp C
Saturated suction temperature, circuit C
17
-
°C
Compressor Suction Tmp C
Compressor suction temperature, circuit C
18
-
°C
Discharge Gas Temp cir C
Discharge gas temperature, circuit C
19
-
°C
Motor Temperature cir C
Motor temperature, circuit C
20
-
°C
Optional Space Temp
Optional space temperature
21
-
°C
CHWS Temperature
Master/slave common water temperature
22
-
°C
CHWS Heat Temp
Master/slave heating temperature
23
-
°C
External Temperature
External temperature
24
-
°C
Cooler Heater Temp
Evaporator heater temperature
25
-
°C
Circuit C Heater Temp
Heater temperature, circuit C
26
-
°C
Economizer Gas Temp A
Economizer gas temperature, circuit A
27
-
°C
Economizer Gas Temp B
Economizer gas temperature, circuit B
28
-
°C
Economizer Gas Temp C
Economizer gas temperature, circuit C
29
-
°C
Dry Cool Leav Water Tmp
Dry Cooler Leaving Water Temperature (units
fitted with a dry cooler)
*Depends on the selected language (English by default).
PRESSURE – Pressures
No.
Status
Unit
Displayed text*
Description
1
-
kPa
Discharge Pressure A
Discharge pressure, circuit A
2
-
kPa
Main Suction Pressure A
Suction pressure, circuit A
3
-
kPa
Oil Pressure A
Oil pressure, circuit A
4
-
kPa
Oil Pressure DifferenceA
Oil pressure difference, circuit A
5
-
kPa
Economizer Pressure A
Economizer pressure, circuit A
6
-
kPa
Discharge Pressure B
Discharge pressure, circuit B
7
-
kPa
Main Suction Pressure B
Suction pressure, circuit B
8
-
kPa
Oil Pressure B
Oil pressure, circuit B
9
-
kPa
Oil Pressure DifferenceB
Oil pressure difference, circuit B
10
-
kPa
Economizer Pressure B
Economizer pressure, circuit B
11
-
kPa
Discharge Pressure C
Discharge pressure, circuit C
12
-
kPa
Main Suction Pressure C
Suction pressure, circuit C
13
-
kPa
Oil Pressure C
Oil pressure, circuit C
14
-
kPa
Oil Pressure DifferenceC
Oil pressure difference, circuit C
15
-
kPa
Economizer Pressure C
Economizer pressure, circuit C
INPUTS – Inputs status
No.
Status
Unit
Displayed text*
Description
1
open/close
-
Remote On/Off Switch
Remote On/Off switch
2
open/close
-
Remote HeatCool Switch
Remote heating/cooling selection switch
3
open/close
-
Remote Reclaim Switch
Remote reclaim switch
4
open/close
-
Free Cooling Disable Sw
Free cooling disable switch
5
open/close
-
Remote Setpoint Switch
Setpoint selection switch
6
open/close
-
Limit Switch 1
Demand limit switch 1
7
open/close
-
Limit Switch 2
Demand limit switch 2
8
open/close
-
Oil Level Input A
Oil level input, circuit A
9
open/close
-
Oil Level Input B
Oil level input, circuit B
10
open/close
-
Oil Level Input C
Oil level input, circuit C
11
-
A
Motor Current A
Motor current, circuit A
12
-
A
Motor Current B
Motor current, circuit B