20
No.
Status
Unit
Displayed text*
Description
37
-
-
Fan Staging Number
Fan stage
38
off/on
-
Discharge valve Open out
Discharge valve open output
39
off/on
-
Dischrge valve Close out
Discharge valve close output
40
-
-
Discharge valve status
Discharge valve status
41
off/on
-
Bypass valve Open out
Bypass valve open output
42
off/on
-
Bypass valve Close out
Bypass valve close output
43
-
-
Bypass valve status
Bypass valve status
44
off/on
-
Refrigerant Pump Out
Refrigerant pump output
45
-
kPa
Pump Inlet Pressure
Pump inlet pressure
46
-
kPa
Pump Outlet Pressure
Pump outlet pressure
47
-
kPa
Pump Differential Press.
Pump differential pressure
48
0 to 100
%
EXV position
EXV position
49
-
°C
Free cooling Liquid Tmp
Free cooling liquid temperature
50
-
^C
Free cooling Subcool Tmp
Free cooling subcooling temperature
51
-
^C
Free cooling Subcool Spt
Free cooling subcooling setpoint
*Depends on the selected language (English by default).
SETPOINT – Setpoint table
No.
Status
Default
Unit
Displayed text*
Description
1
-28.9 to 26
6.7
°C
Cooling Setpoint 1
Cooling setpoint 1
2
-28.9 to 26
6.7
°C
Cooling Setpoint 2
Cooling setpoint 2
3
-28.9 to 26
6.7
°C
Cooling Ice Setpoint
Ice storage setpoint
4
0.1 to 11.1
0.6
^C
Cooling Ramp Loading
Cooling ramp loading setpoint
5
26.7 to 63**
37.8
°C
Heating Setpoint 1**
Heating setpoint 1
6
26.7 to 63**
37.8
°C
Heating Setpoint 2**
Heating setpoint 2
7
0.1 to 11.1
0.6
^C
Heating Ramp Loading
Heating ramp loading setpoint
8
3.9 to 50
23.9
°C
Cool Changeover Setpt
Cooling changeover setpoint
9
0 to 46.1
17.8
°C
Heat Changeover Setpt
Heating changeover setpoint
10
26.7 to 60
35
°C
Water Val Condensing Stp
Water valve condensing setpoint
11
0 to 100
100
%
Switch Limit Setpoint 1
Limit setpoint switch 1
12
0 to 100
100
%
Switch Limit Setpoint 2
Limit setpoint switch 2
13
0 to 100
100
%
Switch Limit Setpoint 3
Limit setpoint switch 3
14
35 to 50
50
°C
Reclaim Setpoint
Heat reclaim setpoint
15
2.8 to 15
5
^C
Reclaim Deadband
Heat reclaim deadband
*Depends on the selected language (English by default).
** 26.7 to 70.0°C range for units with HFO.
NOTE:
Since specific units may not include certain options, some tables provided in the document contain parameters
that cannot be configured for a given unit.
6.3 - Alarms menu
Icon
Displayed text*
Description
Reset Alarms
Alarm reset
Current Alarms
Current alarms
Alarm History
Alarm History
Major Alarm History
Major alarm history
*Depends on the selected language (English by default).